FS-8700-19_Metasys_N2 Driver Manual
Page 30 of 51
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2296
Toll_Free
: 888-509-1970
Digital Output Modules
Relative Item
Signal Condition
Read/Write Johnson Tag
Description
0
Byte
Write
DOT
Digital output options
1
Word
Write
DO@
Source of digital output module
2
Word
Write
FB@
Source of feedback signal
3
Word
Write
DOF@
Output forcing logic connection
4
FP
Write
HRO
Output high range
5
FP
Write
LRO
Output low range
6
FP
Write
FST
PAT output full stroke time/DAT cycle
7
FP
Write
DB
PAT deadband
8
FP
Write
HLO
Output high limit
9
FP
Write
LLO
Output low limit
10
FP
Write
OFL
Output % value in forcing mode
11
FP
Write
OUT
Output module output value %
12
Byte
Write
DOC
Logic output control and status
13
Word
Write
INC@
DDC increase logic connection
14
Word
Write
DEC@
DDC decrease logic connection
15
Word
Write
ENL@
Limit function enable logic connection
Extension Modules
Relative Item
Signal Condition
Read/Write
Johnson Tag
Description
0
Word
Write
XTIOMAP
Extension module I/O map
1
Word
Write
XTIOTYP
Extension module I/O type
2
Word
Write
XTIOMOD
Extension module I/O mode
3
Byte
Write
XTADX
Extension module address 0-255
4
Word
Write
XTI1@
Point connection - I1
5
Word
Write
XTI2@
Point connection - I2
6
Word
Write
XTI3@
Point connection - I3
7
Word
Write
XTI4@
Point connection - I4
8
Word
Write
XTI5@
Point connection - I5
9
Word
Write
XTI6@
Point connection - I6
10
Word
Write
XTI7@
Point connection - I7
11
Word
Write
XTI8@
Point connection - I8
12
FP
Write
XTHR01
High output range point 1
13
FP
Write
XTLR01
Low output range point 1
14
FP
Write
XTHR02
High output range point 2
15
FP
Write
XTLR02
Low output range point 2
16
FP
Write
XTHR03
High output range point 3
17
FP
Write
XTLR03
Low output range point 3
18
FP
Write
XTHR04
High output range point 4
19
FP
Write
XTLR04
Low output range point 4
20
FP
Write
XTHR05
High output range point 5
21
FP
Write
XTLR05
Low output range point 5
22
FP
Write
XTHR06
High output range point 6
23
FP
Write
XTLR06
Low output range point 6
24
FP
Write
XTHR07
High output range point 7
25
FP
Write
XTLR07
Low output range point 7
26
FP
Write
XTHR08
High output range point 8
27
FP
Write
XTLR08
Low output range point 8
28
FP
Write
XTHIA1
High alarm limit point 1
29
FP
Write
XTLOA1
Low alarm limit point 1
30
FP
Write
XTHIA2
High alarm limit point 2
31
FP
Write
XTLOA2
Low alarm limit point 2
32
FP
Write
XTHIA3
High alarm limit point 3
33
FP
Write
XTLOA3
Low alarm limit point 3
34
FP
Write
XTHIA4
High alarm limit point 4
35
FP
Write
XTLOA4
Low alarm limit point 4
36
FP
Write
XTHIA5
High alarm limit point 5
37
FP
Write
XTLOA5
Low alarm limit point 5