Appendix D.2. Metasys DC9100 Memory Map
Note: The DC9100 is not currently supported by the FieldServer MetasysN2 Driver.
The information below is for interest and future use only.
PAGE 0
Item
DEC
Item
HEX
Signal Condition Read/Write
Johnson
Tag
Description
0
0 Byte
Read
MODL
Device model. Value always either 2 or
12
1
1 FP
Read
INP1
Analog input 1
2
2 FP
Read
INP2
Analog input 2
3
3 FP
Read
INP3
Analog input 3
4
4 FP
Read
INP4
Analog input 4
5
5 FP
Read
INP5
Analog input 5
6
6 FP
Read
INP6
Analog input 6
7
7 FP
Read
INP7
Analog input 7
8
8 FP
Read
INP8
Analog input 8
9
9 FP
Read
NCM1
Numeric calculation modul result
10 A
FP
Read
NCM2
Numeric calculation modul result
11 B
FP
Read
NCM3
Numeric calculation modul result
12 C
FP
Read
NMC4
Numeric calculation modul result
13 D
FP
Write
REC1
Remote constant 1
14 E
FP
Write
REC2
Remote constant 2
15 F
FP
Write
REC3
Remote constant 3
16
10 FP
Write
REC4
Remote constant 4
17
11 FP
Write
OUT1
Control output 1
18
12 FP
Write
OUT2
Control output 2
19
13 FP
Write
OUT3
Control output 3
20
14 FP
Write
OUT4
Control output 4
21
15 FP
Write
OUT5
Control output 5
22
16 FP
Write
OUT6
Control output 6
23
17 FP
Write
OUT7
Control output 7
24
18 FP
Write
OUT8
Control output 8
25
19 FP
Write
WSP1
Working setpoint 1
26 1A
FP
Write
WSP2
Working setpoint 2
27 1B
FP
Write
WSP3
Working setpoint 3
28 1C
FP
Write
WSP4
Working setpoint 4
29 1D
FP
Write
WSP5
Working setpoint 5
30 1E
FP
Write
WSP6
Working setpoint 6
31 1F
FP
Write
WSP7
Working setpoint 7
32
20 FP
Write
WSP8
Working setpoint 8
33
21 Word
Read
STW1
Status word 1
34
22 Word
Read
STW2
Status word 2
35
23 Word
Read
STW3
Status word 3
36
24 Word
Read
STW4
Status word 4
37
25 Word
Read
STW5
Status word 5
38
26 Word
Read
STW6
Status word 6
39
27 Word
Read
STW7
Status word 7
40
28 Word
Read
STW8
Status word 8
41
29 Word
Write
DOUT
Logic output DDC control
42 2A
Byte
Write
CHLD
Hold mode control
43 2B
Byte
Write
COMP
Supervisory mode control