Test for Noncondensables

If head pressure seems high even after cleaning 

coils, optimizing airflow, and other routine 
maintenance, you may have noncondensables 
trapped in the system  Noncondensables can 
reduce efficiency, performance, and put extra 
stress on system components  Noncondensables 
can enter the system in many ways, and your initial 
system service may be following years of poor 
service that introduced the noncondensables 

1.  Use 

ARROWS

 to select the system refrigerant.

2.  Unpower the compressor, but allow the condenser fan to run. 

3.  Connect high side port to the system to view system pressure. 

4.  Clamp one thermocouple to the discharge line.

5.  Clamp the other thermocouple to the liquid line.

6.  Clip the ODDB thermocouple to measure the air entering the 

condenser. 

7.  Monitor all three temperatures until they all stabilize and show the 

same value. 

8.  View the subcooling (SC) calculation on the display.  

The closer SC is to 0.0°, the fewer noncondensables are trapped.  

Depending on the system, a negative SC may suggest a need to 

recover, evacuate, and charge with virgin refrigerant. 

Test Tightness (Pressure Test)

After working on a refrigerant-side component 

of an emptied system, it’s a good idea to 
pressurize the system with dry nitrogen and 
check for pressure drops before evacuation  

1.  Pressurize the system with dry nitrogen. 

Pressure levels vary with 

the equipment you’re testing. Always check with the manufacturer.

2.  Connect the low side (suction line) port to the system and wait for 

the pressure to stabilize. 

You can connect the high side (liquid line) 

as well to help monitor stability, but the pressure differential (P.diF)

calculation is only using the low side sensor. 

3.  Attach SLT clamp to the pipe you’re going to pressurize.  

This temperature is used to compensate for any temperature changes 

between the start and end of the test.  

To deactivate temperature  compensation, unplug or unassign SLT 

before starting the test; SLT will not be shown or used. 

4.  Press 

TEST TIGHTNESS

 to prepare test. 

5.  Press 

ENTER

 to start the test.  

The stopwatch starts.  

Real-time compensated pressure change is labeled P.diF. 

Real-time temperature is labeled SLT.  

Real-time temperature change is labeled ΔT.

6.  Press 

ENTER

 to stop the test.  

The stopwatch, P.diF,  and ΔT freeze.  

If P.diF is negative, there may be a leak in the system.  

If P.diF is positive, SLT or nitrogen temperature may be unstable. 

High and low side pressures and SLT continue to display, but they are 

no longer being used.

7.  Press 

ENTER

 to exit the test. 

•  To save battery life, the screen will turn off after 3 hours of testing, 

but will continue to test. Press any button to turn the screen on.

Содержание SMAN SM380V

Страница 1: ...Fieldpiece SMAN Refrigerant Manifold Micron Gauge 4 Port OPERATOR S MANUAL Model SM480V ...

Страница 2: ...ssure Test Test for Noncondensables Menu 22 Data Logging Auto Power Off APO Temperature Calibration Wireless Measurement Sources Target Superheat TSH Sources Units Vacuum Alarms Backlight Timer Advanced Pressure Calibration Firmware View and Update Restore User Settings Delete Log File Format Internal Flash Drive Maintenance 35 Cleaning Battery Replacement Using Different Refrigerants Specificatio...

Страница 3: ...ent 2 Press center blue button for 2 seconds to turn on your new SMAN manifold 3 Connect your hoses and pipe clamps to the SMAN manifold and to the system 4 View live pressures and temperatures 5 Usearrowbuttonstoselectarefrigerantand view calculations in real time What s Included SM480V SMAN Refrigerant Manifold 4 Port 2 TC24 Type K Pipe Clamp Thermocouples 1 ATA1 Type K Bead Thermocouple w Clip ...

Страница 4: ...he job right the first time Your new Fieldpiece manifold has been upgraded for ultimate field protection and long range wireless communication The fully rubberized case seals and protects from dust bumps and light rain Use the heavy duty hook to hang it in your work vehicle while protected by its large padded soft case ModelSM480Visyourtestinghubatthejobsite In addition to the included thermocoupl...

Страница 5: ...fferential SLT Suction LineTemperature low side LLT Liquid LineTemperature high side ODDB Outdoor Dry BulbTemperature IDWB IndoorWet BulbTemperature LOG Data Logging in Progress Job Job Slot 1 9 of Data Log Span Hours Hrs of Data Logging Interval Seconds Sec Between Logged Measurements R Return Psychrometer S Supply Psychrometer DB Dry Bulb from Psychrometer WB Wet Bulb from Psychrometer DP Dew Po...

Страница 6: ...ht Glass Suction Line Port Liquid Line Port Suction Line Port Valve Liquid Line Port Valve Vacuum Port Valve Refrigerant Port Valve LOW HIGH VAC REF Large port matches perfectly with Fieldpiece Vacuum Pump models VP55 andVP85 Vacuum Port Connect to a refrigerant cylinder directly or to a recovery machine like Fieldpiece model MR45 Refrigerant Port FrontView 11 10 ...

Страница 7: ...mocouple Jack Shown fully inserted 4 Digit Job Link System ID Use when connecting to the Job Link Mobile App for testing and reporting Thermocouple Bumpers Bumpers help secure thermocouple plugs Pipe clamp thermocouples have indents on the plug that line up with the bumper when fully inserted LLT Liquid Line Thermocouple Jack Shown not inserted enough RearView 13 12 ...

Страница 8: ...utomaticallytothisdynamic list of 10 VIEW Select Press VIEW to cycle through ODDB outdoor dry bulb TSH target superheat and T1 T2 middle display bottom display ODDB LivereadingoftherearODDBthermocouplejack ODDBdoes not show if set to manual value page 27 TSH LivetargetsuperheatcalculatedfromODDBandIDWB Eachof these measurements can be live or manually entered page 17 T1 T2 Live simple subtraction ...

Страница 9: ... Follow recommended charging or recovery practices from equipment manufacturer and training When superheat and or subcooling cannot be calculated will be displayed If superheat and or subcooling is negative Below Typical Range will show In rare cases this is normal but usually a thermocouple is disconnected or the selected refrigerant is incorrect Target Superheat TSH Compare target superheat TSH ...

Страница 10: ...alvesoryou llblockthesystemand measurejustthemanifold 9 Turn off your vacuum pump 10 Press ALARM to activate the high alarm and start the stopwatch 11 Once the high alarm level is reached the backlight blinks alarm sounds and the stopwatch stops Press any button other than ENTER to silence alarm 12 Close HIGH and LOW manifold valves Thevacuumsensorisnowblockedfromthesystem page39 Tips for Better E...

Страница 11: ...tem it s a good idea to pressurize the system with dry nitrogen and check for pressure drops before evacuation 1 Pressurize the system with dry nitrogen Pressurelevelsvarywith theequipmentyou retesting Alwayscheckwiththemanufacturer 2 Connect the low side suction line port to the system and wait for the pressure to stabilize Youcanconnectthehighside liquidline aswelltohelpmonitorstability butthepr...

Страница 12: ... calculations suchasSuperheat atchosenspansandintervals Save up to 9 Jobs logs to the internal flash drive MENU LogData 1 Use ARROWS to scroll through Jobs Thedisplaywillalternatebetweenthe freespaceonthedriveand the ofspacethechosenJobuses 2 Press ENTER to select IfaJobalreadyexistsinthatslot useARROWSthenENTERtochoose whetherornotyouwanttosaveoverthatJob 3 Use ARROWS to set the Span total time I...

Страница 13: ...ce water is probably the most accurate and readily available known temperature 32 0 F 0 0 C in the field MENU CalTemp 1 Stabilize a large cup of ice water by stirring Pure distilled water will be the most accurate 2 Immerse the sensing end of the thermocouple in the ice water 3 Use ARROWS to select the temperature you want to calibrate SLT LLT or ODDB 4 Press ENTER to select 5 Use ARROWS to adjust...

Страница 14: ...signed to both Return air and IDWB page 17 when selected Target Superheat TSH Sources Target superheat is calculated from outdoor dry bulb ODDB entering the condenser coil and indoor wet bulb IDWB entering the evaporator coil Assign a wireless psychrometer to return air andpluginathermocoupletoODDBforreal time comparison of target vs actual superheat MENU TSH Sources 1 Use ARROWS to toggle between...

Страница 15: ... Use ARROWS to toggle between high and low alarm 2 Press ENTER to select 3 Use ARROWS to adjust the alarm trigger 4 Press ENTER to select and exit or go to next Press MENU to exit at any time Ifchangesweremade choose whetherornotyouwanttosavechanges The low alarm cannot go higher than the high alarm The high alarm cannot go lower than the low alarm Press ENTER ALARM while in deep vacuum to activat...

Страница 16: ... to attach the ODDB thermocouple bead halfway up the cylinder to measure the temperature of the refrigerant 7 Press VIEW if ODDB is not shown 8 Open both HIGH and LOW side manifold valves 9 Open the refrigerant cylinder valve ThepressureinsidecylindershouldnowbedisplayedonbothHIGH andLOWsidepressuresensors 10 Allow the pressure readings and ODDB temperature to stabilize 11 Press MENU 12 Use ARROWS...

Страница 17: ...foundontheinternalflashdrivethenew versionswillbeshown Choosewhetherornotyouwanttoupdate 3 Once installation begins you will see a bar moving across the screen donE will appear and your SMAN manifold will turn off when finished Press MENU to exit at any time before installation begins During installation buttons are disabled User settings are not deleted Log files are not deleted Restore User Sett...

Страница 18: ...e ARROWS to selectYes or No 2 Press ENTER to select and exit Press MENU to exit at any time If you choose to format it may take a few seconds before returning to standard operation User settings are not deleted Maintenance Cleaning Wipe with damp cloth to clean the exterior Do not use solvents Battery Replacement The batteries must be replaced when the battery life indicator is empty Once the batt...

Страница 19: ...A R407C R407F R408A R409A R410A R413A R414A R414B R416A R417A R417C R420A R421A R421B R422A R422B R422C R422D R424A R427A R428A R434A R438A R448A R449A R450A R452A R452B R453A R454B R458A R500 R501 R502 R503 R507A R508B R513A R600 R600A R601 R601A R744 R1233ZD R1234YF R1234ZE Maximumpressure 580Psig 4000kPa Temperature SensorType Type K thermocouple nickelchromium nickelaluminum JackType 3 Type K ...

Страница 20: ...ercury 50 to 1000 microns 5 of reading 1 Pascal 7 to 133 Pascal 5 of reading 0 01 mBar 0 067 to 1 33 mBar 5 of reading 5 mTorr 50 to 1000 mTorr 5 of reading 0 005Torr 0 067 to 1Torr Wireless Compatibility Latestcompatibilityatwww fieldpiece com Job Link System Minimum Device Requirement BLE 4 0 devices running iOS 7 1 or AndroidTM Kitkat 4 4 Wireless Measurement Source Assignments Suction line tem...

Страница 21: ...is device and its antenna s must not be co located or operating in conjunction with any other antenna or transmitter IMPORTANT NOTE FCC Radiation Exposure Statement This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operated with minimum distance 20cm between the radiator your body IC Statement This device con...

Страница 22: ... of a Fieldpiece product including but not limited to impliedwarrantiesofmerchantabilityandfitness for a particular purpose are limited to the above Fieldpiece shall not be liable for loss of use of the machine or other incidental or consequential damages expenses or economic loss or for any claim of such damage expenses or economic loss State laws vary The above limitations or exclusions may not ...

Страница 23: ...SM480V Fieldpiece Instruments Inc 2019 v17 ...

Отзывы: