27
26
Wireless Measurement Sources
Assign wireless Job Link system tools to
core manifold measurements such as pipe
temperature or to broader measurements such
as refrigerant weights and psychrometrics
Wireless OFF:
Line temperatures (SLT and LLT) are automatically
assigned to their type K jacks.
Wireless ON:
SLT and LLT type K jacks DO NOT override an
assigned wireless source.
MENU/Wireless Sources
1. Use
ARROWS
to scroll through the list of measurements.
2. Press
ENTER
to select.
3. Turn on any wireless sources you want to assign.
If your Job Link system tool has a selector switch, ensure it’s set to
match the measurement.
4. Use
ARROWS
to scroll through detected measurement sources.
Job Link system tools are displayed by their 4 digit ID, usually found
on the back of the tool.
5. Press
ENTER
to select and return to the list of measurements.
• Press
MENU
to exit at any time.
If changes were made, choose
whether or not you want to save changes.
• Most Job Link system tools have a switch that selects a side of the
system. Set it to match the measurement you’re assigning it to.
• Select
Clear
to set a source to its factory default source. This is
useful when you want to use a previously assigned tool at the job
site, but do not want to use it with the SMAN manifold.
• A wireless Return psychrometer is assigned to both Return air and
IDWB (page 17) when selected.
Target Superheat (TSH) Sources
Target superheat is calculated from outdoor
dry bulb (ODDB) entering the condenser coil and
indoor wet bulb (IDWB) entering the evaporator
coil Assign a wireless psychrometer to return air
and plug in a thermocouple to ODDB for real-time
comparison of target vs actual superheat
MENU/TSH Sources
1. Use
ARROWS
to toggle between IDWB and ODDB.
2. Press
ENTER
to select.
3. Use
ARROWS
to scroll through detected measurement sources.
Job Link system tools are displayed by their 4 digit ID, usually found
on the back of the tool. ODDB cannot be set to wireless.
4. Turn on any wireless sources you want to assign.
If your Job Link system tool has a selector switch, ensure it’s set to
match the measurement.
5. Press
ENTER
to select and exit or go to next.
• Press
MENU
to exit at any time.
If changes were made, choose
whether or not you want to save changes.
• Most Job Link system tools have a switch that selects a side of the
system. Set it to match the measurement you’re assigning it to.
• Select
Clear
to set a source to its factory default source. This is
useful when you want to use a previously assigned tool at the job
site, but do not want to use it with the SMAN manifold.
• A wireless Return psychrometer is assigned to both Return air (page
15) and IDWB when selected.
• Turning wireless on/off does not change the assigned source.
• If ODDB is set to a manually set value, the thermocouple jack is
deactivated even if a thermocouple is plugged in.