COLLAR INSTALLATION

This control is shipped with a collar patterned to fi t a single wall round 
vent pipe. To attach this collar to the fl ue, See Figure 4 and follow the 
instructions below.

1. Bend outward the two ears at the front corners of the collar. Bend 

90 degrees, 

1

4

" behind the single hole on the straps.

2. Insert clamping screw in ears on collar and bolt the remainder of 

the collar together.

3. Hold the collar against the side of the fl ue in the exact position it is 

to be installed (shown by dotted lines) and mark the outline of the 
collar on the fl ue.

4. Cut a hole in the fl ue about 

1

2

" inside of this outline.

5. Make a series of cuts about 

1

2

" apart from the edge of this hole to the outline marks.

6. Strap the collar to the fl ue pipe.

7. Bend the tabs formed by the series of cuts outward against the inside of the collar to make a tight joint.

8. Insert the draft control. (See Draft Control Installation and Adjustment Section.)

DRAFT CONTROL INSTALLATION AND ADJUSTMENT

1. Insert the draft control into the collar or tee. The front face of 

the control MUST be plumb and the bearing surfaces MUST 
be level whether the control is on a horizontal, vertical or 
sloping fl ue pipe.

2. Use a spirit level and level accurately. (See Figure 5) Secure 

the control in the collar by tightening the clamping screws. If 
a tee is used or a collar is supplied locally, the control may 
be held in place by sheet metal screws.

DRAFT CONTROL INSTALLATION IN TYPE B VENT PIPE
CAUTION: DO NOT use the supplied collar when mounting draft control to Type B Vent Pipe. Install by using a 
           Type B Vent Pipe Tee.

1. Install a vent pipe reducer or increaser into the inner pipe and fasten using sheet metal screws. (See Figure 5)

2. The opening of the Type B Vent Tee, at the draft control 

mounting location, should be sealed with a high 
temperature sealant or equivalent.

3. Refer to Draft Control Installation Section.

WHAT DRAFT SETTING TO USE

When adjusting the control, two things are essential;

1. The burner must be operating for at least 10 minutes to obtain 

maximum chimney draft.

2. An analysis of the fl ue gases is necessary to determine the 

percentage of CO

2

 and check for presence of CO. 

ADJUSTING THE DRAFT CONTROL WITH 4” MG1

The  control  MUST  be  adjusted  to  the  desired  draft  setting  by 
adding or removing the washer-type weights supported by the 
two chains on the side of the draft control. (See Figure 6) DO 
NOT move the weight attached directly to the gate, this is used 
only for balancing at the factory.

Figure 4

Figure 5

Figure 6

Refer to the appliance instructions and/or to the local gas company for the proper CO

2

 readings and allowable 

CO levels. A rule of thumb for draft setting is between .01” to .03” of water column draft at the appliance outlet. 
(Check equipment requirement.)
Changes  in  the  adjustment  of  the  4”  MG1  control  should  be  made  by  adding  or  removing  the  washer-like 
weights (supplied with the control) to or from the weight holder chain assembly. After the control is adjusted, 
its action will be entirely automatic, the gate will open or close by itself to correct for changes in the draft that 
occur in the chimney.

P/N 46285300 Rev F 01/18

Содержание CK-91FV

Страница 1: ...D COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone 24 VAC SYSTEM CONTROL KIT Designed for use with the SWG Series Power Venter for controlling Natural Gas or L P...

Страница 2: ...asten the flexible conduit from the SWG Venter into the conduit connector Mount the CK 91FV junction box or installer supplied junction box onto the wall or floor joist without straining the flexible...

Страница 3: ...TION DO NOT use the supplied collar when mounting draft control to Type B Vent Pipe Install by using a Type B Vent Pipe Tee 1 Install a vent pipe reducer or increaser into the inner pipe and fasten us...

Страница 4: ...properly adjust the pressure switch as specified above could lead to improper operation of the pressure switch which will result in a hazardous condition and bodily harm THERMOSTAT HEAT ANTICIPATOR A...

Страница 5: ...ignition module or gas valve if standing pilot which would normally be 24 volts hot on a call for heat With spark ignition systems this terminal could be TH W 24 V THS or T1 depending on the spark ig...

Страница 6: ...Install the GSK spill switches per instruction and connect to the red wire and the thermal door switch per diagram Wire the venter motor and controls in accordance with the National Electrical Code ma...

Страница 7: ...couple circuit halting the gas flow to the pilot and burner 3 Wait 2 to 3 minutes Reset the spillage switches and light the pilot then perform a second safety spillage test Steps 1 and 2 CAUTION If fo...

Страница 8: ...Pressure Switch 46284200 GSK 3 Spillage Switch 46086400 Post Purge Timer 46282800 Pressure Switch 46083000 TCA 1 Thermocouple Adaptor 46082700 REPAIR AND REPLACEMENT PARTS TROUBLE SHOOTING HINTS 1 Ven...

Отзывы: