DRAFT CONTROL INSTALLATION
CAUTION:  This  draft  control  is  shipped  as  a  single  acting  draft 
control. If the draft control is not being used on a gas draft induced 
furnace,  remove  the  gate  stop  on  the  draft  control  ring  before 
installing.

MOUNTING JUNCTION BOX

The junction box can be mounted at the venter or remotely mounted 
away from the venter. (See Figure 1 & Figure 2)

1. Remove  one  of  the  knockouts  from  the  side  of  the  junction 

box where the pressure switch is mounted. Install the fl exible 
conduit connector onto the CK-91FV junction box and secure 
with  fastening  nut.  If  remote  mounting  the  CK-91FV  junction 
box,  mount  the  fl exible  conduit  connector  onto  a  2"  x  4" 
installer supplied junction box.

2. Fasten  the  fl exible  conduit  from  the  SWG  Venter  into  the 

conduit connector. Mount the CK-91FV junction box or installer 
supplied  junction  box  onto  the  wall  or  fl oor  joist  without 
straining the fl exible conduit. Fasten the CK-91FV junction box 
through  the  four  dimpled  locations  on  the  base  of  the  box. 
(See Figure 3)

PRESSURE SWITCH SENSING TUBE INSTALLATION

1. Attach the 

1

4

" tubing connector to the pressure tube on the 

SWG Venter. (See Figure 3)

2. Connect the supplied 

1

4

" aluminum tubing to the tubing 

connector. Route the tubing to the CK-91FV junction box and 
connect the tubing to the pressure switch. When routing the 
tubing, avoid kinking the tubing by bending the tubing too 
sharply. 

For remote mounted CK-91FV Junction Box, use a 

1

4

" OD copper, 

aluminum or plastic tubing and route the tubing to avoid contact 
with any heat source.

Figure 1

Figure 2

Figure 3

Typical Vent System Layout

P/N 46285300 Rev F 01/18

Содержание CK-91FV

Страница 1: ...D COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone 24 VAC SYSTEM CONTROL KIT Designed for use with the SWG Series Power Venter for controlling Natural Gas or L P...

Страница 2: ...asten the flexible conduit from the SWG Venter into the conduit connector Mount the CK 91FV junction box or installer supplied junction box onto the wall or floor joist without straining the flexible...

Страница 3: ...TION DO NOT use the supplied collar when mounting draft control to Type B Vent Pipe Install by using a Type B Vent Pipe Tee 1 Install a vent pipe reducer or increaser into the inner pipe and fasten us...

Страница 4: ...properly adjust the pressure switch as specified above could lead to improper operation of the pressure switch which will result in a hazardous condition and bodily harm THERMOSTAT HEAT ANTICIPATOR A...

Страница 5: ...ignition module or gas valve if standing pilot which would normally be 24 volts hot on a call for heat With spark ignition systems this terminal could be TH W 24 V THS or T1 depending on the spark ig...

Страница 6: ...Install the GSK spill switches per instruction and connect to the red wire and the thermal door switch per diagram Wire the venter motor and controls in accordance with the National Electrical Code ma...

Страница 7: ...couple circuit halting the gas flow to the pilot and burner 3 Wait 2 to 3 minutes Reset the spillage switches and light the pilot then perform a second safety spillage test Steps 1 and 2 CAUTION If fo...

Страница 8: ...Pressure Switch 46284200 GSK 3 Spillage Switch 46086400 Post Purge Timer 46282800 Pressure Switch 46083000 TCA 1 Thermocouple Adaptor 46082700 REPAIR AND REPLACEMENT PARTS TROUBLE SHOOTING HINTS 1 Ven...

Отзывы: