Group Number
Maximum
Nodes
Description
1
1
Lifeline reports the device status and allows for assigning single device only (main controller
by default).
2
5
On/Off (IN1) is assigned to IN1 input terminal (uses Basic command class).
3
5
On/Off (IN2) is assigned to IN2 input terminal (uses Basic command class).
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further
enhanced features.
IMPORTANT:
Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the
desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the
same logic applies: Values greater than 32768 may needed to be given as negative values too.
Parameter 20: Input 1 - operating mode
This parameter allows to choose mode of 1st input (IN1). Change it depending on connected device.
Size: 1 Byte, Default Value: 2
Setting
Description
0
Normally closed alarm input (Notification)
1
Normally open alarm input (Notification)
2
Monostable button (Central Scene)
3
Bistable button (Central Scene)
4
Analog input without internal pull-up (Sensor Multilevel)
5
Analog input with internal pullup (Sensor Multilevel)
Parameter 21: Input 2 - operating mode
This parameter allows to choose mode of 2nd input
Size: 1 Byte, Default Value: 2
Setting
Description
0
Normally closed alarm input (Notification CC)
1
Normally open alarm input (Notification CC)
2
Monostable button (Central Scene CC)
3
Bistable button (Central Scene CC)
4
Analog input without internal pull-up (Sensor Multilevel CC)
5
Analog input with internal pullup (Sensor Multilevel CC)
Parameter 24: Inputs orientation
This parameter allows reversing operation of IN1 and IN2 inputs without changing the wiring. Use in case of incorrect wiring.
Size: 1 Byte, Default Value: 0
Setting
Description
0
default (IN1 - 1st input, IN2 - 2nd input)
1
reversed (IN1 - 2nd input, IN2 - 1st input)
Parameter 25: Outputs orientation
This parameter allows reversing operation of OUT1 and OUT2 inputs without changing the wiring. Use in case of incorrect wiri ng.
Size: 1 Byte, Default Value: 0
Setting
Description
0
default (OUT1 - 1st output, OUT2 - 2nd output)
1
reversed (OUT1 - 2nd output, OUT2 - 1st output)
Parameter 40: Input 1 - sent scenes
This parameter defines which actions result in sending scene ID and attribute assigned to them (see 9: Activating scenes). Parameter is relevant only if parameter
20 is set to 2 or 3.
Size: 1 Byte, Default Value: 0