FG Wilson Generating Set Скачать руководство пользователя страница 27

24

TABLE 13. kVA/kW AMPERAGE AT VARIOUS VOLTAGES

(0.8 Power Factor)

kVA

kW

208V

220V

240V

380V

400V

440V

460V

480V

600V

2400V

33000V

4160V

6.3

5

17.5

16.5

15.2

9.6

9.1

8.3

8.1

7.6

6.1

9.4

7.5

26.1

24.7

22.6

14.3

13.6

12.3

12

11.3

9.1

12.5

10

34.7

33

30.1

19.2

18.2

16.6

16.2

15.1

12

18.7

15

52

49.5

45

28.8

27.3

24.9

24.4

22.5

18

25

20

69.5

66

60.2

38.4

36.4

33.2

32.4

30.1

24

6

4.4

3.5

31.3

25

87

82.5

75.5

48

45.5

41.5

40.5

37.8

30

7.5

5.5

4.4

37.5

30

104

99

90.3

57.6

54.6

49.8

48.7

45.2

36

9.1

6.6

5.2

50

40

139

132

120

77

73

66.5

65

60

48

12.1

8.8

7

62.5

50

173

165

152

96

91

83

81

76

61

15.1

10.9

8.7

75

60

208

198

181

115

109

99.6

97.5

91

72

18.1

13.1

10.5

93.8

75

261

247

226

143

136

123

120

113

90

22.6

16.4

13

100

80

278

264

240

154

146

133

130

120

96

24.1

17.6

13.9

125

100

347

330

301

192

182

166

162

150

120

30

21.8

17.5

156

125

433

413

375

240

228

208

204

188

150

38

27.3

22

187

150

520

495

450

288

273

249

244

225

180

45

33

26

219

175

608

577

527

335

318

289

283

264

211

53

38

31

250

200

694

660

601

384

364

332

324

301

241

60

44

35

312

250

866

825

751

480

455

415

405

376

300

75

55

43

375

300

1040

990

903

576

546

498

487

451

361

90

66

52

438

350

1220

1155

1053

672

637

581

568

527

422

105

77

61

500

400

1390

1320

1203

770

730

665

650

602

481

120

88

69

625

500

1735

1650

1504

960

910

830

810

752

602

150

109

87

750

600

2080

1980

1803

1150

1090

996

975

902

721

180

131

104

875

700

2430

2310

2104

1344

1274

1162

1136

1052

842

210

153

121

100

0

800

2780

2640

2405

1540

1460

1330

1300

1203

962

241

176

139

112

5

900

3120

2970

2709

1730

1640

1495

1460

1354

1082

271

197

156

125

0

1000

3470

3300

3009

1920

1820

1660

1620

1504

1202

301

218

174

156

3

1250

4350

4130

3765

2400

2280

2080

2040

1885

1503

376

273

218

187

5

1500

5205

4950

4520

2880

2730

2490

2440

2260

1805

452

327

261

218

8

1750

5280

3350

3180

2890

2830

2640

2106

528

380

304

250

0

2000

6020

3840

3640

3320

3240

3015

2405

602

436

348

281

2

2250

6780

4320

4095

3735

3645

3400

2710

678

491

392

312

5

2500

7520

4800

4560

4160

4080

3765

3005

752

546

435

375

0

3000

9040

5760

5460

4980

4880

4525

3610

904

654

522

437

5

3500

10550

6700

6360

5780

5660

5285

4220

1055

760

610

500

0

4000

12040

7680

7280

6640

6480

6035

4810

1204

872

695

Содержание Generating Set

Страница 1: ...GENERATING SET INSTALLATION MANUAL...

Страница 2: ...stions in this installation manual you will be able to plan an economical efficient generating set installation with operating characteristics suitable to each particular application You can make you...

Страница 3: ...ersions for Measurements of Water Table 8 Barometric Pressures and Boiling Points of Water at Various Altitudes Table 9 Conversions of Units of Flow Table 10 Conversions of Units of Pressure and Head...

Страница 4: ...r alternator lifting lugs For lifting the generating set lift points are provided on the baseframe Shackles and chains of suitable length and lifting capacity must be used and a spreader bar is requir...

Страница 5: ...bration isolation between the baseframe and floor Other effects of engine vibration can be minimised by providing flexible connections between the engine and fuel lines exhaust system radiator air dis...

Страница 6: ...or fan helps to maintain room temperature in the desirable range In providing ventilation the objective is to maintain the room air at a comfortable temperature that is cool enough for efficient opera...

Страница 7: ...on an exit ventilator opening should be located on the opposite outside wall to exhaust warm air See Figure 5 3 Both the inlet and exit ventilators should have louvres for weather protection These may...

Страница 8: ...length of pipe within the room the type of insulation used and whether the silencer is located within the room or outside It it usual to insulate the exhaust piping and silencer so that heat radiatio...

Страница 9: ...a flue with a furnace or other equipment since there is danger that back pressure caused by one will adversely affect operation of the others Such multiple use of a flue should be attempted only if it...

Страница 10: ...tion materials to protect personnel and to reduce room temperature A sufficient layer of suitable insulating material surrounding the piping and silencer and retained by a stainless steel or aluminium...

Страница 11: ...length of straight pipe for each elbow and adding it to the total length of pipe For elbows and flexible sections the equivalent length of straight pipe is calculated as follows 45 Elbow Length ft 0 7...

Страница 12: ...ing the choice of these two configurations provides flexibility of installation such as horizontal or vertical above engine on outside wall etc The side inlet type permits 90 change of direction witho...

Страница 13: ...the oil cooler if one is fitted and through passages in the engine block and head Hot coolant emerging from the engine is cooled and recirculated through the engine Cooling devices are commonly coolan...

Страница 14: ...the generating set Air requirements for cooling a particular FG Wilson generator are given in the specification sheet The radiator cooling air must be relatively clean to avoid clogging the radiator c...

Страница 15: ...high static head of the remote radiator coolant The engine pump circulates engine coolant through the engine and the element of the heat exchanger A separate pump circulates radiator coolant between t...

Страница 16: ...lly followed 10 FUEL SUPPLY A dependable fuel supply system must assure instant availability of fuel to facilitate starting and to keep the engine operating This requires at a minimum a small day tank...

Страница 17: ...re extended vent to prevent overflow through the vent sealed fuel level gauges on the basetank and no manual fill facility All other connections on top of the tank must be sealed to prevent leakage Fu...

Страница 18: ...el System 4 is not compatible with the polyethylene fuel tanks standard on smalle generator sets The optional metal tank is required A 2001 Series control system or above is required Distance A on Fig...

Страница 19: ...n refills Particularly with standby generators the availability of fuel delivery service will determine the number of operating hours that must be provided for Don t depend on quick service the very d...

Страница 20: ...s must undergo major modifications to accommodate this type of fuel For use of jet fuel please consult FG Wilson Reliable operation of diesel engines may vary from one fuel to another depending on man...

Страница 21: ...gas spark ignition engines are used in Generating Sets that are intended for continuous service For standby service however this is not recommended The natural gas supply and regulation system adds s...

Страница 22: ...2 M2 Hectare Km2 1 In2 1 0 006944 0 00064516 1 Ft2 144 1 0 0929 1 Acre 43 560 1 0 0015625 4 047 0 4047 0 004047 1 Mile2 27 878 400 640 1 2 589 998 258 99 2 5899 1 M2 1550 10 764 1 1 Hectare 107 639 2...

Страница 23: ...s Hr Meters Sec Meters Mi n Km Hr 1 Foot Sec 1 60 0 0 6818 0 3048 18 288 1 Foot Min 0 0167 1 0 1136 0 00508 1 Mile Hr 1 467 88 1 26 822 1 6093 1 Meter Sec 3 281 196 848 1 1 Meter Min 0 05468 0 03728 1...

Страница 24: ...udes Barometric Pressure Water Boiling Point Ft Inches of Mercury lb in2 Feet Water F C Sea Level 29 92 14 69 33 95 212 0 100 1000 28 86 14 16 32 60 210 1 99 2000 27 82 13 66 31 42 208 3 98 3000 26 81...

Страница 25: ...0 0013 1 in Hg 25 4 1 13 5951 1 1330 0 49115 0 03453 0 0334 3 386 1 in H2O 1 86827 0 0736 1 0 0833 0 03613 0 00254 0 0025 0 249 1 ft H2O 22 4192 0 8827 12 1 0 43352 0 030479 0 0295 2 989 1 lb in 51 7...

Страница 26: ...ctric Motor Horsepower Output HP IxVxEff x PF 746 3 xIxVxEff x PF 746 IxVxEff 746 Amperes I When Horsepower is known HPx 746 VxEff x PF HPx 746 3 xVxEff x PF HPx 746 VxEff Amperes I When Kilowatts are...

Страница 27: ...0 694 660 601 384 364 332 324 301 241 60 44 35 312 250 866 825 751 480 455 415 405 376 300 75 55 43 375 300 1040 990 903 576 546 498 487 451 361 90 66 52 438 350 1220 1155 1053 672 637 581 568 527 422...

Страница 28: ...34 lb Specific FuelConsumption lb BHP hr FuelCons US gal hr x FuelSpec Wt lb US gal BHP Specific FuelConsumption kg BHP hr Spec Fuel Cons lb BHP hr BHP Electrical Motor Horsepower Electrical Motor Hor...

Страница 29: ...n assumption that the lower the BMEP the greater the expected engine life and reliability In practice it is not a reliable indicator of engine performance for the following reasons The formula favours...

Страница 30: ...ent is the Hertz Hz equivalent to 1 cycle per second CPS FREQUENCY BAND The permissible variation from a mean value under steady state conditions FREQUENCY DRIFT Frequency drift is a gradual deviation...

Страница 31: ...ly in normal service without exceeding the allowable temperature rises RATED POWER The stated or guaranteed net electric output which is obtainable continuously from a generating set when it is functi...

Страница 32: ...rees apart A three phase system may be either 3 wire or 4 wire 3 wires and a neutral UNINTERRUPTABLE POWER SUPPLY UPS A system designed to provide power without delay or transients during any period w...

Страница 33: ...276 851 INSTALL DOC 0601 GROUP HEADQUARTERS Old Glenarm Road Larne Co Antrim BT40 1EJ Northern Ireland United Kingdom Telephone 44 028 2826 1000 Fax 44 028 2826 1111...

Отзывы: