11. SELECTING FUELS

FOR STANDBY 
DEPENDABILITY

The types of fuels available for diesel engines, vary
from highly volatile jet fuels and kerosene to the
heavier fuel oils.  Most diesel engines are capable
of burning a wide range of fuels within these
extremes.  The following information will assist you
in selecting the type of fuel that will afford the best
overall performance and reliability of your
Generating Set.

11.1 Types Of Fuel Oil

The quality of fuel oil can be a dominant factor in
satisfactory engine life and performance.  A large
variety of fuel oils are marketed for diesel engine
use. Their properties depend upon the refining
practices employed and the nature of the crude oils
from which they are produced.  For example, fuel
oils may be produced within the boiling range of
148 to 371

°

C (300 to 700°F), having many possible

combinations of other properties.

The additional contaminants present in low grade
fuels may result in darker exhaust and more
pronounced odour.  This may be objectionable in
hospitals, offices commercial and urban locations.
Thus, location, application and environmental
conditions should be considered when selecting
fuel.

The Generating Set owner may elect to use a low
grade fuel because high-grade fuels are not readily
available in his area or because he can realise a net
saving with low grade fuels despite higher engine
maintenance costs.  In that case, frequent
examination of lubrication oil should be made to
determine sludge formation and the extent of lube
oil contamination.

Aside from the various grades of fuel oil commonly
used in diesel engines, aircraft jet fuels also are
sometimes used, especially in circumstances where
the jet fuels are more readily available than
conventional fuels.  Jet fuels are lower in B.T.U.
content and lubrication quality than conventional
fuels.  As a result, some diesel fuel systems must
undergo major modifications to accommodate this
type of fuel.  For use of jet fuel please consult FG
Wilson.

Reliable operation of diesel engines may vary from
one fuel to another, depending on many factors,
including fuel characteristics and engine operating
conditions.

The fuels commonly known as high-grade fuels
seldom contribute to the formation of harmful
engine deposits and corrosion.  On the other hand,
while refining improves the fuel, it also lowers the
B.T.U. or heat value of the fuel.  As a result, the
higher grade fuels develop slightly less power than
the same quantity of low grade fuel.  This is
usually more than offset by the advantages of high
grade fuels such as quicker starts and less frequent
overhauls.  Before using low-grade fuels, therefore,
some understanding of the problems and extra
costs that may be encountered is necessary.

Fuels with high sulphur content cause corrosion,
wear and deposits in the engine.  Fuels that are not
volatile enough or don't ignite rapidly may leave
harmful deposits in the engine and may cause poor
starting or running under adverse operating
conditions.  The use of low grade fuels may require
the use of high priced, higher detergent lubricating
oils and more frequent oil changes.

11.2 Fuel Selection Guide

Specify fuel properties according to the following
chart.

Final
Boiling
Point

Cetane
Number
(Min)

Sulphur
Number
(Max)

Winter

290

°

C (550ºF)

45

0.5 %

Summer

315

°

C (600ºF)

40

0.5 %

Selecting a fuel that keeps within these
specifications will tend to reduce the possibility of
harmful deposits and corrosion in the engine, both
of which could result in more frequent overhauls
and greater maintenance expense.  Specify exact
fuel properties to your local fuel supplier.

11.3 Maintaining Fresh Fuel

Most fuels deteriorate if they stand unused for a
period of many months.  With standby generators it
is preferable to store only enough fuel to support a
few days or even only eight hours of continuous
running of the Generating Set so that normal engine
testing will turn over a tank full within a year and a
half.

Содержание Generating Set

Страница 1: ...GENERATING SET INSTALLATION MANUAL...

Страница 2: ...stions in this installation manual you will be able to plan an economical efficient generating set installation with operating characteristics suitable to each particular application You can make you...

Страница 3: ...ersions for Measurements of Water Table 8 Barometric Pressures and Boiling Points of Water at Various Altitudes Table 9 Conversions of Units of Flow Table 10 Conversions of Units of Pressure and Head...

Страница 4: ...r alternator lifting lugs For lifting the generating set lift points are provided on the baseframe Shackles and chains of suitable length and lifting capacity must be used and a spreader bar is requir...

Страница 5: ...bration isolation between the baseframe and floor Other effects of engine vibration can be minimised by providing flexible connections between the engine and fuel lines exhaust system radiator air dis...

Страница 6: ...or fan helps to maintain room temperature in the desirable range In providing ventilation the objective is to maintain the room air at a comfortable temperature that is cool enough for efficient opera...

Страница 7: ...on an exit ventilator opening should be located on the opposite outside wall to exhaust warm air See Figure 5 3 Both the inlet and exit ventilators should have louvres for weather protection These may...

Страница 8: ...length of pipe within the room the type of insulation used and whether the silencer is located within the room or outside It it usual to insulate the exhaust piping and silencer so that heat radiatio...

Страница 9: ...a flue with a furnace or other equipment since there is danger that back pressure caused by one will adversely affect operation of the others Such multiple use of a flue should be attempted only if it...

Страница 10: ...tion materials to protect personnel and to reduce room temperature A sufficient layer of suitable insulating material surrounding the piping and silencer and retained by a stainless steel or aluminium...

Страница 11: ...length of straight pipe for each elbow and adding it to the total length of pipe For elbows and flexible sections the equivalent length of straight pipe is calculated as follows 45 Elbow Length ft 0 7...

Страница 12: ...ing the choice of these two configurations provides flexibility of installation such as horizontal or vertical above engine on outside wall etc The side inlet type permits 90 change of direction witho...

Страница 13: ...the oil cooler if one is fitted and through passages in the engine block and head Hot coolant emerging from the engine is cooled and recirculated through the engine Cooling devices are commonly coolan...

Страница 14: ...the generating set Air requirements for cooling a particular FG Wilson generator are given in the specification sheet The radiator cooling air must be relatively clean to avoid clogging the radiator c...

Страница 15: ...high static head of the remote radiator coolant The engine pump circulates engine coolant through the engine and the element of the heat exchanger A separate pump circulates radiator coolant between t...

Страница 16: ...lly followed 10 FUEL SUPPLY A dependable fuel supply system must assure instant availability of fuel to facilitate starting and to keep the engine operating This requires at a minimum a small day tank...

Страница 17: ...re extended vent to prevent overflow through the vent sealed fuel level gauges on the basetank and no manual fill facility All other connections on top of the tank must be sealed to prevent leakage Fu...

Страница 18: ...el System 4 is not compatible with the polyethylene fuel tanks standard on smalle generator sets The optional metal tank is required A 2001 Series control system or above is required Distance A on Fig...

Страница 19: ...n refills Particularly with standby generators the availability of fuel delivery service will determine the number of operating hours that must be provided for Don t depend on quick service the very d...

Страница 20: ...s must undergo major modifications to accommodate this type of fuel For use of jet fuel please consult FG Wilson Reliable operation of diesel engines may vary from one fuel to another depending on man...

Страница 21: ...gas spark ignition engines are used in Generating Sets that are intended for continuous service For standby service however this is not recommended The natural gas supply and regulation system adds s...

Страница 22: ...2 M2 Hectare Km2 1 In2 1 0 006944 0 00064516 1 Ft2 144 1 0 0929 1 Acre 43 560 1 0 0015625 4 047 0 4047 0 004047 1 Mile2 27 878 400 640 1 2 589 998 258 99 2 5899 1 M2 1550 10 764 1 1 Hectare 107 639 2...

Страница 23: ...s Hr Meters Sec Meters Mi n Km Hr 1 Foot Sec 1 60 0 0 6818 0 3048 18 288 1 Foot Min 0 0167 1 0 1136 0 00508 1 Mile Hr 1 467 88 1 26 822 1 6093 1 Meter Sec 3 281 196 848 1 1 Meter Min 0 05468 0 03728 1...

Страница 24: ...udes Barometric Pressure Water Boiling Point Ft Inches of Mercury lb in2 Feet Water F C Sea Level 29 92 14 69 33 95 212 0 100 1000 28 86 14 16 32 60 210 1 99 2000 27 82 13 66 31 42 208 3 98 3000 26 81...

Страница 25: ...0 0013 1 in Hg 25 4 1 13 5951 1 1330 0 49115 0 03453 0 0334 3 386 1 in H2O 1 86827 0 0736 1 0 0833 0 03613 0 00254 0 0025 0 249 1 ft H2O 22 4192 0 8827 12 1 0 43352 0 030479 0 0295 2 989 1 lb in 51 7...

Страница 26: ...ctric Motor Horsepower Output HP IxVxEff x PF 746 3 xIxVxEff x PF 746 IxVxEff 746 Amperes I When Horsepower is known HPx 746 VxEff x PF HPx 746 3 xVxEff x PF HPx 746 VxEff Amperes I When Kilowatts are...

Страница 27: ...0 694 660 601 384 364 332 324 301 241 60 44 35 312 250 866 825 751 480 455 415 405 376 300 75 55 43 375 300 1040 990 903 576 546 498 487 451 361 90 66 52 438 350 1220 1155 1053 672 637 581 568 527 422...

Страница 28: ...34 lb Specific FuelConsumption lb BHP hr FuelCons US gal hr x FuelSpec Wt lb US gal BHP Specific FuelConsumption kg BHP hr Spec Fuel Cons lb BHP hr BHP Electrical Motor Horsepower Electrical Motor Hor...

Страница 29: ...n assumption that the lower the BMEP the greater the expected engine life and reliability In practice it is not a reliable indicator of engine performance for the following reasons The formula favours...

Страница 30: ...ent is the Hertz Hz equivalent to 1 cycle per second CPS FREQUENCY BAND The permissible variation from a mean value under steady state conditions FREQUENCY DRIFT Frequency drift is a gradual deviation...

Страница 31: ...ly in normal service without exceeding the allowable temperature rises RATED POWER The stated or guaranteed net electric output which is obtainable continuously from a generating set when it is functi...

Страница 32: ...rees apart A three phase system may be either 3 wire or 4 wire 3 wires and a neutral UNINTERRUPTABLE POWER SUPPLY UPS A system designed to provide power without delay or transients during any period w...

Страница 33: ...276 851 INSTALL DOC 0601 GROUP HEADQUARTERS Old Glenarm Road Larne Co Antrim BT40 1EJ Northern Ireland United Kingdom Telephone 44 028 2826 1000 Fax 44 028 2826 1111...

Отзывы: