FG Wilson Generating Set Скачать руководство пользователя страница 18

15

With this system, the basetank must include an
overflow via the return line, sealed fuel level gauges
and no manual fill facility. All other connections on
top of the tank must be sealed to prevent leakage.
Fuel System 2 is not compatible with the
polyethylene fuel tanks standard on smaller
generator sets.  The optional metal tank is required.
A 2001 Series control system (or above) is required.

Distance ‘A’ in Figure 10.2 is limited to 1400mm for
all generator sets with metal basetanks.

Fuel System

 

4

:  Some installations may require a

system where fuel is pumped from a free standing
bulk tank (see Figure 10.4).  This pumped system
would only be used if gravity feed is not possible
from the bulk tank to the basetank.

Figure 10.4:Typical Layout with Fuel System 4

The key components are the above ground bulk
fuel tank (item 1), remote fuel system controls (item
2) located in the generator set control panel, an AC
Fuel Pump (item 3), a DC motorised fuel valve (item
4), fuel level switches in the basetank (item 5), the
fuel supply line (item 6), an extended vent/return
line (continuous rise) on the basetank  (item 7), a
fuel strainer (item 8) and an isolating valve at the
bulk tank (item 9).

When set to automatic, the system operates as
follows: low fuel level in the basetank is sensed by
the fuel level sensor.  The DC motorised valve is
opened and the pump begins to pump fuel from the
bulk tank to the basetank through the supply line.
To help ensure that clean fuel reaches the engine,
fuel from the bulk tank is strained just prior to the
motorised valve.  When the basetank is full, as
sensed by the

 

fuel level sensor, the pump stops

and

 

the motorised valve is closed. Any overflow

into the basetank or overpressure in the basetank
will flow back to the bulk tank via the extended
vent.
With this system, the basetank must include an
overflow via the return line, sealed fuel level gauges
and no manual fill facility. All other connections on

top of the tank must be sealed to prevent leakage.
Fuel System 4 is not compatible with the
polyethylene fuel tanks standard on smalle
generator sets.  The optional metal tank is required.
A 2001 Series control system (or above) is required.

Distance ‘A’ on Figure 10.4 is limited to 1400mm for
all generator sets with metal basetanks.  Note that
the maximum restriction caused by friction losses
and height of the return line should not exceed 2
psi.

10.3 Tank Construction

Fuel tanks are usually made of welded sheet steel or
reinforced plastic.  If an old fuel tank is used, be
sure it is made of a proper material.  It should be
cleaned thoroughly to remove all rust, scale and
foreign deposits.

Connections for fuel suction and return lines must
be separated as much as possible to prevent re-
circulation of hot fuel and to allow separation of
any gases entrained in the fuel.  Fuel suction lines
should extend below the minimum fuel level in the
tank.  Where practical, a low point in the tank
should be equipped with a drain valve or plug, in an
accessible location, to allow periodic removal of
water condensation and sediment.  Or a hose may
be inserted through the tank's filter neck when
necessary to suck out water and sediment.

The filler neck of the bulk fuel tank should be
located in a clean accessible location.  A removable
wire screen of approximately 1.6 mm (1/16 inch)
mesh should be placed in the filler neck to prevent
foreign material from

entering the tank.  The filler neck cap or the highest
point in the tank should be vented to maintain
atmospheric pressure on the fuel and to provide
pressure relief in case a temperature rise causes the
fuel to expand.  It will also prevent a vacuum as fuel
is consumed. The tank may be equipped with a fuel
level gauge - either a sight gauge or a remote
electrical gauge.

10.4 Fuel Lines

The fuel lines can be of any fuel compatible material
such as steel pipe or flexible hoses that will tolerate
environmental conditions.

Fuel delivery and return lines should be at least as
large as the fitting sizes on the engine, and overflow
piping should be one size larger.  For longer runs of
piping or low ambient temperatures the size of these
lines should be increased to ensure adequate flow.

Содержание Generating Set

Страница 1: ...GENERATING SET INSTALLATION MANUAL...

Страница 2: ...stions in this installation manual you will be able to plan an economical efficient generating set installation with operating characteristics suitable to each particular application You can make you...

Страница 3: ...ersions for Measurements of Water Table 8 Barometric Pressures and Boiling Points of Water at Various Altitudes Table 9 Conversions of Units of Flow Table 10 Conversions of Units of Pressure and Head...

Страница 4: ...r alternator lifting lugs For lifting the generating set lift points are provided on the baseframe Shackles and chains of suitable length and lifting capacity must be used and a spreader bar is requir...

Страница 5: ...bration isolation between the baseframe and floor Other effects of engine vibration can be minimised by providing flexible connections between the engine and fuel lines exhaust system radiator air dis...

Страница 6: ...or fan helps to maintain room temperature in the desirable range In providing ventilation the objective is to maintain the room air at a comfortable temperature that is cool enough for efficient opera...

Страница 7: ...on an exit ventilator opening should be located on the opposite outside wall to exhaust warm air See Figure 5 3 Both the inlet and exit ventilators should have louvres for weather protection These may...

Страница 8: ...length of pipe within the room the type of insulation used and whether the silencer is located within the room or outside It it usual to insulate the exhaust piping and silencer so that heat radiatio...

Страница 9: ...a flue with a furnace or other equipment since there is danger that back pressure caused by one will adversely affect operation of the others Such multiple use of a flue should be attempted only if it...

Страница 10: ...tion materials to protect personnel and to reduce room temperature A sufficient layer of suitable insulating material surrounding the piping and silencer and retained by a stainless steel or aluminium...

Страница 11: ...length of straight pipe for each elbow and adding it to the total length of pipe For elbows and flexible sections the equivalent length of straight pipe is calculated as follows 45 Elbow Length ft 0 7...

Страница 12: ...ing the choice of these two configurations provides flexibility of installation such as horizontal or vertical above engine on outside wall etc The side inlet type permits 90 change of direction witho...

Страница 13: ...the oil cooler if one is fitted and through passages in the engine block and head Hot coolant emerging from the engine is cooled and recirculated through the engine Cooling devices are commonly coolan...

Страница 14: ...the generating set Air requirements for cooling a particular FG Wilson generator are given in the specification sheet The radiator cooling air must be relatively clean to avoid clogging the radiator c...

Страница 15: ...high static head of the remote radiator coolant The engine pump circulates engine coolant through the engine and the element of the heat exchanger A separate pump circulates radiator coolant between t...

Страница 16: ...lly followed 10 FUEL SUPPLY A dependable fuel supply system must assure instant availability of fuel to facilitate starting and to keep the engine operating This requires at a minimum a small day tank...

Страница 17: ...re extended vent to prevent overflow through the vent sealed fuel level gauges on the basetank and no manual fill facility All other connections on top of the tank must be sealed to prevent leakage Fu...

Страница 18: ...el System 4 is not compatible with the polyethylene fuel tanks standard on smalle generator sets The optional metal tank is required A 2001 Series control system or above is required Distance A on Fig...

Страница 19: ...n refills Particularly with standby generators the availability of fuel delivery service will determine the number of operating hours that must be provided for Don t depend on quick service the very d...

Страница 20: ...s must undergo major modifications to accommodate this type of fuel For use of jet fuel please consult FG Wilson Reliable operation of diesel engines may vary from one fuel to another depending on man...

Страница 21: ...gas spark ignition engines are used in Generating Sets that are intended for continuous service For standby service however this is not recommended The natural gas supply and regulation system adds s...

Страница 22: ...2 M2 Hectare Km2 1 In2 1 0 006944 0 00064516 1 Ft2 144 1 0 0929 1 Acre 43 560 1 0 0015625 4 047 0 4047 0 004047 1 Mile2 27 878 400 640 1 2 589 998 258 99 2 5899 1 M2 1550 10 764 1 1 Hectare 107 639 2...

Страница 23: ...s Hr Meters Sec Meters Mi n Km Hr 1 Foot Sec 1 60 0 0 6818 0 3048 18 288 1 Foot Min 0 0167 1 0 1136 0 00508 1 Mile Hr 1 467 88 1 26 822 1 6093 1 Meter Sec 3 281 196 848 1 1 Meter Min 0 05468 0 03728 1...

Страница 24: ...udes Barometric Pressure Water Boiling Point Ft Inches of Mercury lb in2 Feet Water F C Sea Level 29 92 14 69 33 95 212 0 100 1000 28 86 14 16 32 60 210 1 99 2000 27 82 13 66 31 42 208 3 98 3000 26 81...

Страница 25: ...0 0013 1 in Hg 25 4 1 13 5951 1 1330 0 49115 0 03453 0 0334 3 386 1 in H2O 1 86827 0 0736 1 0 0833 0 03613 0 00254 0 0025 0 249 1 ft H2O 22 4192 0 8827 12 1 0 43352 0 030479 0 0295 2 989 1 lb in 51 7...

Страница 26: ...ctric Motor Horsepower Output HP IxVxEff x PF 746 3 xIxVxEff x PF 746 IxVxEff 746 Amperes I When Horsepower is known HPx 746 VxEff x PF HPx 746 3 xVxEff x PF HPx 746 VxEff Amperes I When Kilowatts are...

Страница 27: ...0 694 660 601 384 364 332 324 301 241 60 44 35 312 250 866 825 751 480 455 415 405 376 300 75 55 43 375 300 1040 990 903 576 546 498 487 451 361 90 66 52 438 350 1220 1155 1053 672 637 581 568 527 422...

Страница 28: ...34 lb Specific FuelConsumption lb BHP hr FuelCons US gal hr x FuelSpec Wt lb US gal BHP Specific FuelConsumption kg BHP hr Spec Fuel Cons lb BHP hr BHP Electrical Motor Horsepower Electrical Motor Hor...

Страница 29: ...n assumption that the lower the BMEP the greater the expected engine life and reliability In practice it is not a reliable indicator of engine performance for the following reasons The formula favours...

Страница 30: ...ent is the Hertz Hz equivalent to 1 cycle per second CPS FREQUENCY BAND The permissible variation from a mean value under steady state conditions FREQUENCY DRIFT Frequency drift is a gradual deviation...

Страница 31: ...ly in normal service without exceeding the allowable temperature rises RATED POWER The stated or guaranteed net electric output which is obtainable continuously from a generating set when it is functi...

Страница 32: ...rees apart A three phase system may be either 3 wire or 4 wire 3 wires and a neutral UNINTERRUPTABLE POWER SUPPLY UPS A system designed to provide power without delay or transients during any period w...

Страница 33: ...276 851 INSTALL DOC 0601 GROUP HEADQUARTERS Old Glenarm Road Larne Co Antrim BT40 1EJ Northern Ireland United Kingdom Telephone 44 028 2826 1000 Fax 44 028 2826 1111...

Отзывы: