background image

En-9

13.2.

 

Installing the external connect kit

(1)  Install the cable as shown in the following photograph.
 

Be sure to place the wiring under the tabs.

Tabs

Connector 
CN2 or CN3

13.3.

  

Installing the other optional parts

• Communication kit
• External input and output PCB*
• External input and output PCB box
* Optional External input and output PCB box is necessary for the installation.

Refer to each installation manual for the method of installing the other optional parts.

13.4.

 

Front panel, control box cover replacement

Reinstall by reversing the procedure in “13.1. Front panel, control box cover removal”.

(1)   Replace the control box cover and screws.

Screw

Screw

(2)   Open a hole in the front panel for the remote controller cable to pass through. 
 * 

 

Choose from 4 knockout holes marked on the inside of the front panel.

(3)  Replace the front cover.
 

Refer to “9.2. Front panel installation”.

14.  SPECIAL INSTALLATION METHODS

Group control system

A number of indoor units can be operated at the same time using a single remote controller.
*When connecting different types of indoor units (such as wall mounted, cassette, duct, or 

other types), some functions may be restricted.

(1)  Connect multiple indoor units in a system.

A

B

C

D

E

I.U.

I.U.

I.U.

I.U.

Remote 
controller

A, B, C, D, E : Remote controller cable.
A+B+C+D+E 

 500 m

Select the appropriate cable depending on the total wiring length.

Total wiring length of remote 

controller cable

(A+B+C+D+E)

Cross section of cable

500 m or less

0.3-1.25 mm

2

 

Example of wiring method (2-wire type)

Y1 Y2

Remote 
controller cable

Remote controller

PCB or terminal block 
for wired remote controller

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

(2)  

Set the R.C. address (Function setting)

(a) 2-wire 

type

   Automatic setting:
     •  

Addresses will be automatically set when initially starting up this unit. In such a 

case, do not change the R.C. address of the indoor unit, and keep it at the initial 

setting (00).

     •  

Connect up to 16 indoor units in a system.

   Manual setting:
     •  

Only set addresses manually when using different numbers for addresses.
Set the R.C. address of each indoor unit with the wireless remote controller.
 Also set the R.C. address of the wired remote controller. For details, please refer 
to the remote controller installation manual.

   

  *  In manual setting, connect up to 15 indoor units in a system.

   

  *  Do not use the R.C. address “00”.

(b) 3-wire 

type

   Manual setting:
     •  

Set the R.C. address of each indoor unit with the wireless remote controller. 

     •  

Set each R.C. address in sequence from “00”. 

     •  

Connect up to 16 indoor units in a system.

Example of R.C. address setting (3-wire type)

RC AD 

00

RC AD 

01

RC AD

02

RC AD 

03

Remote 
controller

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Remote controller address setting

(

...  Factory setting)

Function 

Number

Setting Value

Setting Description

00

00

2-wired type: Setting prohibited

3-wired type: Unit no. 0

01

Unit no. 1

02 ~ 13

Unit no. 2 ~ Unit no. 13

14

Unit no. 14

15

Unit no. 15

* Do not use the same setting value.
* After completing the Function Setting, be sure to disconnect the power supply and then 

reconnect it.

NOTES:

 

Set the R.C. address by the wireless remote controller.

9387082050-02_IM.indb   9

9387082050-02_IM.indb   9

13/3/2018   PM 5:00:25

13/3/2018   PM 5:00:25

Содержание LMTA Series

Страница 1: ...B CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experi...

Страница 2: ... screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller 1 UTY RVN M For air conditioner operation 3 wire type Wired Remote Controller 2 UTY RNR Z For air conditioner operation 2 wire type Wired Remote Controller 2 UTY RLR For air conditioner operation 2 wire type ...

Страница 3: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wa...

Страница 4: ... Use a hexagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping a...

Страница 5: ... nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by you...

Страница 6: ... indoor unit to the outdoor unit unless it is specified 8 FINISHING 1 Insulate between pipes Insulate suction and discharge pipes separately For rear right and bottom piping overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap 2 Temporarily fasten the connection cable along the connection pipe with vinyl tape Wrap to...

Страница 7: ...e heat exchanger When installing or removing parts of the air conditioner be sure that the wire is not caught by any parts or pulled hard It may result in damage or malfunction of the air conditioner 4 Remove 10 screws Screws Wire cover Screws 10 places Caps 4 places Wire cover NOTES When replacing the front panel do not scratch or damage the louver 5 The front panel is pulled to the front raising...

Страница 8: ...bles to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When interlocking with external device Connector CN3 PCB Connected device Relay Locally purchased or When displaying Operation Stop Connector CN3 PCB Connected device Resistor LED Operation behavior If function setting 60 is set to 00 Refer to 16 FUNCTION SETTING 12 1 3 Connection methods Wire modification...

Страница 9: ... type Y1Y2 Remote controller cable Remote controller PCB or terminal block for wired remote controller Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 2 Set the R C address Function setting a 2 wire type Automatic setting Addresses will be automatically set when initially starting up this unit In such a case do not change the R C address of the indoor unit and keep it at the initial settin...

Страница 10: ...10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP buttons to select the setting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function setting information Please con fir...

Страница 11: ... 01 Factory setting Function Number Setting Value Setting Description 48 00 Both 01 Wired remote controller Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function Number Setting Value Setting Description 49 00 Disable 01 Enable ...

Страница 12: ...ror 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display P...

Отзывы: