En-4

6.4. Installing the wall hook bracket

(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically. 

If the wall hook bracket is titled, water will drip to the 

fl

 oor.

(2) Install the wall hook bracket so that it is strong enough to support the weight of the unit.

• Fasten the wall hook bracket to the wall with 5 or more screws through the holes near 

the outer edge of the bracket.

• Check that there is no rattle at the wall hook bracket.

Wall hook bracket

Tapping screws (large, accessories)

 CAUTION

Install the wall-hook bracket both horizontally and vertically aligned. 
Misaligned installation may cause water leakage.

6.5. Forming the drain hose and pipe

 CAUTION

•  Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.

•  When inserting the drain hose, no other material than water should be applied. 

Application of other material than water will cause deterioration of the hose, and may 

cause water leakage.

•  After you remove a drain hose, be sure to attach the drain cap.

•  When you secure the piping and drain hose with tape, arrange the drain hose so that 

it is at the bottom of the piping.

•  For drain hose piping in low temperature environment, you need to apply freeze 

protection to prevent a frozen drain hose. 

After cooling operation is performed in low temperature environment, (when outdoor 

temperature under 0 °C,) water in the drain hose could be frozen. Frozen drain water 

will block the water 

fl

 ow in the hose, and may cause water leakage at the indoor unit.

[Rear piping, Right piping, Bottom piping]

• Install the indoor unit piping in the direction of the wall hole and bind the drain hose 

and pipe together with vinyl tape.

• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

 

 

 

 

 

 

 

Right piping

Bind with vinyl tape

Indoor unit drain hose 
(bottom)

Pipe (top)
Rear piping

Bottom piping

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

Drain cap

Indoor unit 
drain hose

Remove the drain cap by pull-
ing at the projection at the end 
of the cap with pliers, etc.

For left outlet piping, cut 
off the piping outlet cutting 
groove with a hacksaw.

 

 

 

 

 

 

Installing the Drain cap 

Use a hexagonal wrench 4 mm at opposite side to 
insert the drain cap, till the drain cap contacts the tip 
of the drain cock.

No gap

Hexagonal 
wrench

Drain 

cock

Drain cap

 CAUTION

Insert the drain hose and drain cap into the drain port, making sure that it comes 
in contact with the back of the drain port, and then mount it. If the drain hose is not 
connected properly, leaking will occur.

•  For left piping and left rear piping, align the marks on the wall hook bracket and shape 

the connection pipe.

•  Bend the connection piping at the bend radius of 100 mm or more and install no more 

than 35 mm from the wall.

•  After passing the indoor piping and drain hose through the wall hole, hang the indoor unit 

on the hooks at the top and bottom of the wall hook bracket.

Wall hook 
bracket

Alignment marks

Small piping

Connection 
piping

Large piping

[Installing the indoor unit]

•  Hang the indoor unit from the hooks at the top of the wall hook bracket.
•  Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Indoor unit

Wall hook bracket

(Spacer)

 

 

 

 

 

 

 

Top hooks

Indoor 
unit

(Fitting)

Bottom hooks

Wall hook 
bracket

•  After hooking the indoor unit to the top hook, hook the 

fi

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

6.6. Flare connection (Pipe connection)

 CAUTION

Tighten the flare nuts with a torque wrench using the specified tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

6.6.1. Flaring

Use special pipe cutter and 

fl

 are tool designed for R410A pipework.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor unit(s) and outdoor 

unit respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use 

the special R410A 

fl

 are tool, or the conventional 

fl

 are tool. Leakage of refrigerant may 

result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Die

A

Pipe

B

L

Check if [L] is flared uniformly 
and is not cracked or scratched.

9387082050-02_IM.indb   4

9387082050-02_IM.indb   4

13/3/2018   PM 5:00:25

13/3/2018   PM 5:00:25

Содержание LMTA Series

Страница 1: ...B CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experi...

Страница 2: ... screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller 1 UTY RVN M For air conditioner operation 3 wire type Wired Remote Controller 2 UTY RNR Z For air conditioner operation 2 wire type Wired Remote Controller 2 UTY RLR For air conditioner operation 2 wire type ...

Страница 3: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wa...

Страница 4: ... Use a hexagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping a...

Страница 5: ... nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by you...

Страница 6: ... indoor unit to the outdoor unit unless it is specified 8 FINISHING 1 Insulate between pipes Insulate suction and discharge pipes separately For rear right and bottom piping overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap 2 Temporarily fasten the connection cable along the connection pipe with vinyl tape Wrap to...

Страница 7: ...e heat exchanger When installing or removing parts of the air conditioner be sure that the wire is not caught by any parts or pulled hard It may result in damage or malfunction of the air conditioner 4 Remove 10 screws Screws Wire cover Screws 10 places Caps 4 places Wire cover NOTES When replacing the front panel do not scratch or damage the louver 5 The front panel is pulled to the front raising...

Страница 8: ...bles to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When interlocking with external device Connector CN3 PCB Connected device Relay Locally purchased or When displaying Operation Stop Connector CN3 PCB Connected device Resistor LED Operation behavior If function setting 60 is set to 00 Refer to 16 FUNCTION SETTING 12 1 3 Connection methods Wire modification...

Страница 9: ... type Y1Y2 Remote controller cable Remote controller PCB or terminal block for wired remote controller Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 2 Set the R C address Function setting a 2 wire type Automatic setting Addresses will be automatically set when initially starting up this unit In such a case do not change the R C address of the indoor unit and keep it at the initial settin...

Страница 10: ...10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP buttons to select the setting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function setting information Please con fir...

Страница 11: ... 01 Factory setting Function Number Setting Value Setting Description 48 00 Both 01 Wired remote controller Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function Number Setting Value Setting Description 49 00 Disable 01 Enable ...

Страница 12: ...ror 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display P...