En-6

(3)  Connect the end of the connection cable fully into the terminal block.

1 2 3

25 mm

65 mm

Earth (ground) wire

7.3.  How to connect wiring to the terminals

Caution when wiring cable

To strip off the insulation of a lead wire, always use a special tool such as a wire stripper. 
If there is no special tool, carefully strip off the insulation by using a knife or other utensil. 
(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure to connect to the 

terminal block. 

(2)  Securely clamp the ring terminals to the wires by using an appropriate tool so that the 

wires do not come loose. 

Strip : 10 mm 

Ring terminal

Sleeve

(3) Connect 

speci

fi

 ed wires securely, and fasten them so that there is no stress applied on 

the terminals. 

(4)  Use a screwdriver with an appropriate bit size to tighten the terminal screws. Using of 

screwdriver with inappropriate bit size will damage the screw heads, and the screws 
will not be tightened properly.

(5)  Do not overtighten the terminal screws. Otherwise, the screws may break.

Screw with special washer

Wire

Ring terminal

Terminal blocks

Wire

Screw with special washer

Ring terminal

(6)  See the table for the terminal screw tightening torques.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

 CAUTION

•  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit or branch box. Incorrect wiring may cause a 

fi

 re.

•  Connect the connection cables 

fi

 rmly to the terminal block. Imperfect installation may 

cause a 

fi

 re.

•  When 

fi

 xing the connection cable with the cable clamp, always fasten the cable at the 

plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric 

leakage may occur.

•  Always connect the earth (ground) wire. Improper earthing (grounding) work can 

cause electric shocks.

•  Do not use the earth (ground) screw for the indoor unit to the outdoor unit unless it is 

speci

fi

 ed.

8. FINISHING 

 (1)  Insulate between pipes.

•  Insulate suction and discharge pipes separately.
•  For rear, right, and bottom piping, overlap the connection pipe heat insulation and 

indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.

 (2)  Temporarily fasten the connection cable along the connection pipe with vinyl tape. 

(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water 
does not enter.)

 (3)  Fasten the connection pipe to the outside wall with a saddle, etc.
 (4)  Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain 

water and wind cannot blow in.

 (5)  Fasten the drain hose to the outside wall, etc.

*Locally purchased

Pipe

Saddle*

Outside wall cap*

Sealer putty*

(Outdoors)

Wall

Overlap the insulation

Vinyl tape

Wrap with cloth tape 

Cloth tape

Drain hose

Pipe

Connection pipe 
(heat insulation)

Indoor unit pipe
(heat insulation)

Bind the pipes together 
so that there is no gap.

Drain hose insulation is used 

when the diameter of gas pipe is 

Ø12.70 or more.

Butt connection pipe (heat 

insulation) against the indoor 

unit pipe (heat insulation) and 

wrap with drain hose insula-

tion so that there is no gap.

Check the following:

GOOD

Drain hose
Saddle

Lifted up

Wave

End in water

PROHIBITED

9.  FRONT PANEL REMOVAL AND INSTALLATION

Intake grille removal

Intake grille installation

b

a

Open the intake 
grille. While gently 
pressing the left 
and right mounting 
shafts of the intake 
grille outward “a”, 
remove the intake 
grille in direction of 
the arrow “b”.

c

While holding the 
grille horizontal, set 
the left and right 
mounting shafts into 
the pillow blocks at 
the top of the panel 
“c”.
To latch each shaft 
properly, insert the 
shaft until it snaps.
Press 4 places on 
the intake grille to 
close it completely.

 9.1. Front panel removal

 (1)  Remove intake grille (Refer to “Intake grille removal”.)
 (2)  Remove 4 caps.
 (3)  Remove wire cover.

9387082050-02_IM.indb   6

9387082050-02_IM.indb   6

13/3/2018   PM 5:00:25

13/3/2018   PM 5:00:25

Содержание LMTA Series

Страница 1: ...B CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experi...

Страница 2: ... screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller 1 UTY RVN M For air conditioner operation 3 wire type Wired Remote Controller 2 UTY RNR Z For air conditioner operation 2 wire type Wired Remote Controller 2 UTY RLR For air conditioner operation 2 wire type ...

Страница 3: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wa...

Страница 4: ... Use a hexagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping a...

Страница 5: ... nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by you...

Страница 6: ... indoor unit to the outdoor unit unless it is specified 8 FINISHING 1 Insulate between pipes Insulate suction and discharge pipes separately For rear right and bottom piping overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap 2 Temporarily fasten the connection cable along the connection pipe with vinyl tape Wrap to...

Страница 7: ...e heat exchanger When installing or removing parts of the air conditioner be sure that the wire is not caught by any parts or pulled hard It may result in damage or malfunction of the air conditioner 4 Remove 10 screws Screws Wire cover Screws 10 places Caps 4 places Wire cover NOTES When replacing the front panel do not scratch or damage the louver 5 The front panel is pulled to the front raising...

Страница 8: ...bles to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When interlocking with external device Connector CN3 PCB Connected device Relay Locally purchased or When displaying Operation Stop Connector CN3 PCB Connected device Resistor LED Operation behavior If function setting 60 is set to 00 Refer to 16 FUNCTION SETTING 12 1 3 Connection methods Wire modification...

Страница 9: ... type Y1Y2 Remote controller cable Remote controller PCB or terminal block for wired remote controller Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 2 Set the R C address Function setting a 2 wire type Automatic setting Addresses will be automatically set when initially starting up this unit In such a case do not change the R C address of the indoor unit and keep it at the initial settin...

Страница 10: ...10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP buttons to select the setting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function setting information Please con fir...

Страница 11: ... 01 Factory setting Function Number Setting Value Setting Description 48 00 Both 01 Wired remote controller Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function Number Setting Value Setting Description 49 00 Disable 01 Enable ...

Страница 12: ...ror 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display P...

Отзывы: