17. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

fl

 ow switching, and other remote control unit operations.

(2)  Air 

fi

 lter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

18. ERROR CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output error 
codes by way of blinking patterns. If you use a wired remote controller, error codes will ap-
pear on the remote control display. See the lamp blinking patterns and error codes in the 
table. An error display is displayed only during operation.

Error display

Wired 

remote 

controller

Error code

Description

Operation 

indicator 

lamp

(green)

Timer 

indicator 

lamp

(orange)

Economy 

indicator 

lamp

(green)

(1)

(1)

Serial communication error

(1)

(2)

• Wired remote controller 

communication error

• Server room control 

communication error

(1)

(5)

Check run unfinished

(1)

(6)

Peripheral unit transmission PCB 
connection error

(2)

(1)

Unit number or Refrigerant circuit 
address setting error
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

•  Connection unit number error 

(indoor secondary unit)
[Simultaneous Multi]

•  Connection unit number error 

(indoor unit or branch unit)
[Flexible Multi]

(2)

(6)

Address setting error in wired 
remote controller system

(2)

(7)

Primary unit, secondary unit set-
up error [Simultaneous Multi]

(3)

(2)

Indoor unit PCB model 
information error

(3)

(5)

Manual auto switch error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit Heat Ex. Middle temp. 
sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error 

(5)

(8)

Intake grille error

(5)

(15)

Indoor unit error

(6)

(2)

Outdoor unit main PCB model 
information error or 
communication error

(6)

(3)

Inverter  error 

(6)

(4)

Active filter error, PFC circuit error 

(6)

(5)

Trip terminal L error

(6)

(10)

Display PCB microcomputers 
communication error  

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid temp. 
sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

(7)

(6)

• 2-way valve temp. sensor error
• 3-way valve temp. sensor error

(7)

(7)

Heat sink temp. sensor error

(8)

(2)

• Sub-cool Heat Ex. gas inlet 

temp. sensor error

• Sub-cool Heat Ex. gas outlet 

temp. sensor error

(8)

(3)

Liquid pipe temp. sensor error

(8)

(4)

Current sensor error

(8)

(6)

• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error

(9)

(4)

Trip detection

(9)

(5)

Compressor rotor position 
detection error 

(9)

(7)

Outdoor unit fan motor error

(9)

(9)

4-way valve error

(10)

(1)

Discharge temp. error

(10)

(3)

Compressor temp. error

(10)

(4)

High pressure error

(10)

(5)

Low pressure error

(13)

(2)

Branch boxes error
[Flexible Multi]

Display mode 

 : 0.5s On / 0.5s Off

 : 0.1s On / 0.1s Off

( ) : Number of flashing

[Troubleshooting with the indoor unit display]

Operation indicator lamp (green)

Timer indicator lamp (orange)

Economy indicator lamp (green)

[Troubleshooting with the Wired Remote Controller Display (Option)]

If an error occurs, the following display will be shown. (“Er” will appear in the set room 
temperature display.)

Error code

9387082050-02_IM.indb   12

9387082050-02_IM.indb   12

13/3/2018   PM 5:00:26

13/3/2018   PM 5:00:26

Содержание LMTA Series

Страница 1: ...B CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experi...

Страница 2: ... screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller 1 UTY RVN M For air conditioner operation 3 wire type Wired Remote Controller 2 UTY RNR Z For air conditioner operation 2 wire type Wired Remote Controller 2 UTY RLR For air conditioner operation 2 wire type ...

Страница 3: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wa...

Страница 4: ... Use a hexagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping a...

Страница 5: ... nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by you...

Страница 6: ... indoor unit to the outdoor unit unless it is specified 8 FINISHING 1 Insulate between pipes Insulate suction and discharge pipes separately For rear right and bottom piping overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap 2 Temporarily fasten the connection cable along the connection pipe with vinyl tape Wrap to...

Страница 7: ...e heat exchanger When installing or removing parts of the air conditioner be sure that the wire is not caught by any parts or pulled hard It may result in damage or malfunction of the air conditioner 4 Remove 10 screws Screws Wire cover Screws 10 places Caps 4 places Wire cover NOTES When replacing the front panel do not scratch or damage the louver 5 The front panel is pulled to the front raising...

Страница 8: ...bles to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When interlocking with external device Connector CN3 PCB Connected device Relay Locally purchased or When displaying Operation Stop Connector CN3 PCB Connected device Resistor LED Operation behavior If function setting 60 is set to 00 Refer to 16 FUNCTION SETTING 12 1 3 Connection methods Wire modification...

Страница 9: ... type Y1Y2 Remote controller cable Remote controller PCB or terminal block for wired remote controller Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 2 Set the R C address Function setting a 2 wire type Automatic setting Addresses will be automatically set when initially starting up this unit In such a case do not change the R C address of the indoor unit and keep it at the initial settin...

Страница 10: ...10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP buttons to select the setting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function setting information Please con fir...

Страница 11: ... 01 Factory setting Function Number Setting Value Setting Description 48 00 Both 01 Wired remote controller Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function Number Setting Value Setting Description 49 00 Disable 01 Enable ...

Страница 12: ...ror 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display P...

Отзывы: