VABF-S4-1-V2B1...
28
Festo – VABF-S4-1-V2B1... – 1705c English
Malfunction
Remedy
Possible cause
Required vacuum is
not obtained
Insufficient supply of air to the valve
terminal
–
Increase supply pressure
–
Increase supply cross section
–
Install an additional supply
plate directly next to the vacuum
block; optionally create a
separate pressure zone, see
manual VTSA/VTSA-F
Soft-start valve installed on the valve
terminal
If the valve terminal is pneumatically
actuated, first send an electrical
release signal (14) to deactivate
vacuum generation. Only revert to
vacuum generation after full
operating pressure of the
valve terminal has built up (12).
Vacuum block does
not revert to the
air-saving function
Insufficient supply of air to the valve
terminal
–
Increase supply pressure
–
Increase supply cross section
–
Install an additional supply
plate directly next to the vacuum
block; optionally create a
separate pressure zone, see
manual VTSA/VTSA-F.
Switching thresholds or hysteresis
set incorrectly
Correct switching thresholds and/or
hysteresis
Channel A and/or B set as N/C
contact (NC)
Set channel A and B as N/O contact
(NO)
Channel A and/or B set as window
comparator
Set channel A and B as threshold
value comparator
Er01
1)
Pressure sensor defective
Send device to Festo
Er09
1)
Value below measuring range with In A
Maintain permitted measuring range.
If the permitted maximum values are
exceeded, the pressure sensor must
be replaced. Send device to Festo.
Er10
1)
Measuring range exceeded with In A
Er11
1)
Value below measuring range with In B
Er12
1)
Measuring range exceeded with In B
Er17
2)3)
Undervoltage
Maintain operating voltage
1)
7-segments display flashes. Error display in the SHOW mode (
è
Chapter 6.2 “SHOW mode”).
2)
7-segments display flashes. The currently smallest error number is shown.
3)
Outputs are reset automatically (logic 0).
Tab. 8
Fault clearance