2
Fitting and removing the modules
CAUTION
Modules can be damaged by incorrect handling.
•
Do not touch any of the components.
•
Follow the instructions for handling components which
are affected by electrostatic charges.
•
Discharge yourself electrostatically before inserting or
removing modules in order to protect the components
from discharges of static electricity.
A maximum of 1 diagnostic module can be installed in the rack.
The first (left-hand) slot is reserved for the power supply module
(type SPC-200-PWR-AIF). Diagnostic modules can be installed
in any of the remaining slots. In order that the control panel can
be secured, it must overlap the adjacent front panel. The
diagnostic module must not therefore be mounted in the last
slot. Each installed module is identified automatically.
Removing the modules
1. Switch off the power and compressed air supply.
2. Disconnect the connecting cable on the front of the module
and remove it.
3. Slide the two safety catches sideways to unlock them
(see diagram below).
4. Take hold of the module by the front plate and extract it.
5. Fill any remaining empty slots with blank panels.
SPC200-MMI-DIAG
12
9804NH
Содержание SPC200-MMI-DIAG
Страница 2: ...Deutsch 3 English 11 Festo AG Co D 73726 Esslingen 1998 SPC200 MMI DIAG 9804NH 2...
Страница 10: ...SPC200 MMI DIAG 10 9804NH...
Страница 18: ...SPC200 MMI DIAG 18 9804NH...