Festo PDAD Series Скачать руководство пользователя страница 13

Layout of purge air regulation for reducing air consumption 

 

Application note 

 Energy management function at adsorption dryer PDAD 

 1.10                                                      Page 13 of 17 

2.5

 

Use of a pressure sensor for purge regulation 

 

If a pressure sensor is used, it’s best to use a programmable variant. In the final analysis, this type of pressure 

sensor is a pressure transmitter and a process regulator in a single component. Although a programmable 
pressure sensor is a bit more expensive than a simple mechanical pressure switch, it can be much more 
favourably configured. Hysteresis can typically be reduced or eliminated, which permits immediate reaction to 
changes in system pressure which determine air flow. 
If a pressure sensor is used, the dryer is wired to the contacts of a switching relay which are closed in the 
absence of current. When the pressure sensor is activated (figure 3, page 10: e.g. at an overpressure of 6.55 bar 
or 95 

psi), the purge function is shut down via the relay contact until the pressure sensor’s output drops out 

again at the selected pressure value (in this example at an overpressure of 6.2 bar or 90 psi). The point at which 
the switch is released can be adjusted in accordance with the system.  
 

It’s very important to understand that the purge function can 

only

 be shut down at times when little or no air is 

required. If this function is shut down at any other time, the drying agent cartridges may be permanently 
damaged thus resulting in the loss of drying performance, and possibly a mechanical defect as well. The 
cartridges may never be entirely saturated! 

Fundamentally, the solution with a pressure sensor is critical with 

regard to constant dew point reduction.

 

 
The following drawing shows how the above mentioned components might be connected for regulation of a 

dryer’s purge function. Please note that specific details regarding the components are manufacturer

-

independent 

 

the manufacturer’s specifications must be complied with in any case.

 

 

 

Figure 6: 

Use of a pressure sensor for purge regulation (this setup is only an example and the configuration can be changed depending 
on the application) 

Dryer 

regulator 

Pin 2 

Pin 1 (reads out  
+5 V DC signal) 

Signal output 

Return signal 

* Current-free when closed 

 open to deactivate the purge function 

 
 

DC supply power 

Electronic 

pressure switch 

Relay 

S

ig

n

a

o

ut

 

COM

 

Содержание PDAD Series

Страница 1: ...e Energy management function at adsorption dryer PDAD Application note for use of the energy management function at adsorption dryer PDAD Explanation use and layout of purge air regulation for reducin...

Страница 2: ...used for the implementation of safety relevant functions for the protection of personnel and machinery No liability is accepted for claims for damages arising from failure or malfunctioning Otherwise...

Страница 3: ...easonably foreseeable misuse 7 2 4 Environment used in 7 2 5 User groups 7 2 Layout of purge air regulation for reducing air consumption 8 3 1 Nature of the task 8 2 2 Use of a manual switch for purge...

Страница 4: ...onents 1 2 Documentation This application note is intended to supplement existing documents to include the energy management function Catalogue documentation https www festo com cat en gb_gb data doc_...

Страница 5: ...at the interface matter between two phases Adsorption dryers draw the moisture out of the compressed air through the use of a drying agent While adsorption takes place in the first container regenera...

Страница 6: ...g instructions The software is neither provided by Festo nor is it available because the device can be damaged in the event of incorrect settings The PDAD is also equipped with an alarm connection whi...

Страница 7: ...idges may never be entirely saturated In any case checking must be conducted for continuously flawless functioning because the dryer might otherwise fail or errors might occur within the process or th...

Страница 8: ...sure drop although no air consumption is required for the application Compressor start up results in noise in some cases disagreeably at night The temperature in the room might also rise so that appli...

Страница 9: ...y important to understand that the purge function can only be shut down at times when little or no air is required If this function is shut down at any other time the drying agent cartridges may be pe...

Страница 10: ...portant to understand that the purge function can only be shut down at times when little or no air is required If this function is shut down at any other time the drying agent cartridges may be perman...

Страница 11: ...wn until the pressure switch is once again released in this example at an overpressure of 6 2 bar or 90 psi The point at which the switch is released can be adjusted in accordance with the system If i...

Страница 12: ...yer PDAD 1 10 Page 12 of 17 Figure 4 Use of a simple pressure switch for purge regulation Dryer regulator Pin 1 reads out 5 V DC signal Pressure switch installed in the field Signal output Return sign...

Страница 13: ...s example at an overpressure of 6 2 bar or 90 psi The point at which the switch is released can be adjusted in accordance with the system It s very important to understand that the purge function can...

Страница 14: ...tting i e purge air is also active at times when little or no purge air is required There s a plug inserted into the socket for the energy management function EM to this end with pre set jumper see fi...

Страница 15: ...lay contact is opened purge air is deactivated The dryer should be removed from service before conversion or integration In order to remove the device from service disconnect it from supply power and...

Страница 16: ...lay a new cable may not have a wire cross section of any greater than 1 5 sq mm recommended in order to freely fit into the DIN plug insert should have an outside diameter of no more than 6 mm Larger...

Страница 17: ...ections and testing before commissioning All cables must be secured in an appropriate manner The device must be removed from service before conducting any maintenance or repair work Operators and othe...

Отзывы: