Festo PDAD Series Скачать руководство пользователя страница 11

Layout of purge air regulation for reducing air consumption 

 

Application note 

 Energy management function at adsorption dryer PDAD 

 1.10                                                      Page 11 of 17 

2.4

 

Use of a simple pressure switch for purge regulation 

 
Many compressors are furnished with pressure switches which include additional contacts, by means of which the 

dryer’s purge function can be shut down when the compressor is in the discharged state. Unfortunately, many of 

these switches have considerable dead zones or a large hysteresis (difference or reset point between the charge 
(on)  and  discharge  (off)  settings,  which  in  most  cases  cannot  be  changed).  The  amount  of  air  which  can  flow 
through the dryer while the compressor is being discharged must be taken into consideration, because it may be 
considerable (in particular if the hysteresis is large or the receiver is very moist.  
 
A  separate  pressure  switch  is  often  a  better  alternative,  because  the  user  can  adjust  it  independently  of  the 

compressor’s pres

sure switch. The following applies when selecting a separate pressure switch: the smaller the 

hysteresis the better. If a separate pressure switch is used, the dryer is wired to the contacts at the pressure switch 
which  are  closed  in  the  absence  of  current.  When  the  switch  is  activated  (figure  3:  e.g.  at  an  overpressure  of 
6.55 bar  or  95 psi),  the  purge  function  is  shut  down  until  the  pressure  switch  is  once  again  released  (in  this 
example at an overpressure of 6.2 bar or 90 psi). The point at which the switch is released can be adjusted in 
accordance with the system.  
 

If it’s determined that the dew point drops to an unacceptable level, the point at which the switch is released must 

be increased. Please note that many pressure switches have a fixed hysteresis value, in which case the activation 
and deactivation points change in correspondence to each other. 
 

It’s very important to understand that the purge function can 

only

 be shut down at times when little or no air is 

required. If this function is shut down at any other time, the drying agent cartridges may be permanently damaged 
thus resulting in the loss of drying performance, and possibly a mechanical defect as well. The cartridges may 
never be entirely saturated! 

Fundamentally, the solution with a simple pressure switch is critical with regard to 

constant dew point reduction.

 

 

Figure 4 on page 11 shows how the above mentioned components might be connected for regulation of a dryer’s 

purge function. Please note that specific details regarding the components are manufacturer-independent 

 the 

manufacturer’s specifications must be complied with in any case.

 

 
 

 

 

Figure 3: 

Adjustment of the simple pressure switch or pressure sensor 

 
 
 
 
 
 

Purge function off (switch activated) 

Purge function off (switch activated) 

Purge function on (switch deactivated) 

Purge function on 

Adjust depending on system 

(pressure switch deactivation point) 

S

ys

tem

 p

res

su

re (

p

si

g

Содержание PDAD Series

Страница 1: ...e Energy management function at adsorption dryer PDAD Application note for use of the energy management function at adsorption dryer PDAD Explanation use and layout of purge air regulation for reducin...

Страница 2: ...used for the implementation of safety relevant functions for the protection of personnel and machinery No liability is accepted for claims for damages arising from failure or malfunctioning Otherwise...

Страница 3: ...easonably foreseeable misuse 7 2 4 Environment used in 7 2 5 User groups 7 2 Layout of purge air regulation for reducing air consumption 8 3 1 Nature of the task 8 2 2 Use of a manual switch for purge...

Страница 4: ...onents 1 2 Documentation This application note is intended to supplement existing documents to include the energy management function Catalogue documentation https www festo com cat en gb_gb data doc_...

Страница 5: ...at the interface matter between two phases Adsorption dryers draw the moisture out of the compressed air through the use of a drying agent While adsorption takes place in the first container regenera...

Страница 6: ...g instructions The software is neither provided by Festo nor is it available because the device can be damaged in the event of incorrect settings The PDAD is also equipped with an alarm connection whi...

Страница 7: ...idges may never be entirely saturated In any case checking must be conducted for continuously flawless functioning because the dryer might otherwise fail or errors might occur within the process or th...

Страница 8: ...sure drop although no air consumption is required for the application Compressor start up results in noise in some cases disagreeably at night The temperature in the room might also rise so that appli...

Страница 9: ...y important to understand that the purge function can only be shut down at times when little or no air is required If this function is shut down at any other time the drying agent cartridges may be pe...

Страница 10: ...portant to understand that the purge function can only be shut down at times when little or no air is required If this function is shut down at any other time the drying agent cartridges may be perman...

Страница 11: ...wn until the pressure switch is once again released in this example at an overpressure of 6 2 bar or 90 psi The point at which the switch is released can be adjusted in accordance with the system If i...

Страница 12: ...yer PDAD 1 10 Page 12 of 17 Figure 4 Use of a simple pressure switch for purge regulation Dryer regulator Pin 1 reads out 5 V DC signal Pressure switch installed in the field Signal output Return sign...

Страница 13: ...s example at an overpressure of 6 2 bar or 90 psi The point at which the switch is released can be adjusted in accordance with the system It s very important to understand that the purge function can...

Страница 14: ...tting i e purge air is also active at times when little or no purge air is required There s a plug inserted into the socket for the energy management function EM to this end with pre set jumper see fi...

Страница 15: ...lay contact is opened purge air is deactivated The dryer should be removed from service before conversion or integration In order to remove the device from service disconnect it from supply power and...

Страница 16: ...lay a new cable may not have a wire cross section of any greater than 1 5 sq mm recommended in order to freely fit into the DIN plug insert should have an outside diameter of no more than 6 mm Larger...

Страница 17: ...ections and testing before commissioning All cables must be secured in an appropriate manner The device must be removed from service before conducting any maintenance or repair work Operators and othe...

Отзывы: