Festo — MS6(N)-SV-...-E-10V24 — 2021-11e
Technical data
Runtime performance of enable signals
t1
>
5 ms:
Level of EN2 (EN1) must be HIGH (LOW) for min. 5 ms (debounce time/input
filter/stabilisation time).
t2
<
=
75 ms:
maximum permissible delay time between EN1 and EN2.
Exceeding maximum permissible delay time:
–
Product is not pressurised and an error message is output (NECA-…-MP3)
–
Product is not pressurised and an error message is output (NECA-…-MP5)
t3
>
=
15 ms:
Level of EN2 (EN1) must be LOW (HIGH) for min. 15 ms (debounce time/input
filter/stabilisation time).
t4 = 2 ms:
maximum internal time delay caused by the program sequence.
tp1
}
2:
Pressurisation
>
300 ms
tp2
}
3:
Exhausting
>
2 s
Tab. 15: Runtime performance of enable signals