Festo KBS_FEC FC34- 0206NH English
32
7
Commissioning the IPC FEC FC34
General instructions on commissioning
When you first commission the IPC FEC FC34, please ob-
serve the following instructions.
1. Please follow the safety, wiring and emergency stop
instructions.
2. Connect the 24 V DC operating voltage to the terminals
on the terminal strip labelled as Power 24 V and 0 V.
Create a conducting connection between the func-
tional earth and earth potential.
3. Connect at least one sensor to an input, e.g. In 0.1.
4. Connect the 24 V DC operating voltage to the output
terminals (C+, C-) and optionally to an actuator, as il-
lustrated in the following diagram. Please follow the
applicable safety regulations in your company.
5. Switch on the 24 V DC operating voltage (Power). The
Power LED must light up. The status LED for the input
that you assigned must light up if your sensor returns
a “1” signal.
6. Start your programming software. Connect the SM14
programming cable between your programming PC
(ideally at COM1) and the IPC FEC FC34 (COM inter-
face).