Festo KBS_FEC FC34- 0206NH English
37
General information
Protection class
Protection class III. Power supply
units in accordance with IEC 742 /
EN 60742/ VDE 0551 / PELV with
at least 4 kV insulation resistance
or switched mode power supply
units having safe isolation within
the meaning of EN 60950/VDE
0805 are required
1)
I/O connections
Screw-type terminal
Nominal cross-section
2 x 0.75 mm
2
Tightening torque for screws
(screw-type terminals)
max. 0.5 Nm
EMC
EN 61000-6-2, EN 50081-2
1)When switching from “non-PELV circuits” via the relay outputs, the complete unit is to
be assigned to protection class II.