Festo P.BE−K−HSP_HSW−AE 0710a English
21
Connecting the motor unit:
S
Seal unused terminals with the protective caps
supplied.
S
Use a regulated power supply unit with high power
reserve (see Power supply" table).
S
Use the following cables (observe the max. length):
Cable
Max.
Type of accessory
Supply line
Programming line
Pilot line
10 m
2.5 m
30 m
KPWR−MC−1−SUB−9HC−...
KDI−MC−M8−SUB−9−...
KES−MC−1−SUB−9HC−...
Power
supply
HSW−10
HSW−12
HSP−12/16
HSW−16
HSP−25
Nominal voltage
1)
24VDC±10%
Nominal motor current
0.73 A
2 A
5 A
Peak motor current
2.1 A
3.8 A
7.7 A
Power supply unit
2)
24VDC/3A
24VDC/6A
24VDC/10A
External fuse
5 A,
slow−blow
7 A,
slow−blow
10 A,
slow−blow
1)
The tolerance must be complied with directly at the power supply
connection.
2) Power reserve of 20...50% recommended