2
System overview, CTEL system
14
Festo – P.BE-CPX-CTEL-EN – 1411a – English
LED
Meaning
Behaviour
off
CPX system-internal communication OK.
Lights up red
Several causes are possible:
–
CPX system starts momentarily, display then turns off.
–
General error.
X1 … X4 off
No connection to a device.
Lights up green
Device connected, communication OK.
Flashes green
Several causes are possible:
–
Connection established to the device, diagnostics running.
–
I/O length of the recognised device is too large (only in the
tool change mode, (
è
4.1.1)).
Lights up red
Device error. Several causes are possible:
–
Connection to the device interrupted.
–
Error in the I-port communication.
Flashes red
Compatibility error. Several causes are possible:
–
An incompatible device is connected to the corresponding
I-port.
–
The corresponding port is deactivated, but a connected
device is recognised.
All four LEDs flashing red
Configuration error. Several causes are possible:
–
Invalid configuration (e.g. through exceeding of the
available address space).
–
Device was not replaced by another device type, system
restart necessary (only for automatic configuration).
Tab. 2.3
Monitoring of the load supply voltage (PL) takes place in the devices and is passed on to
the CTEL master module.
Since all connected devices use this LED, the display of an error has priority over the dis
play “OK” (LED illuminated green).
The I-port at which the error has occurred can be determined through the FMT/MMI using
the diagnostic messages.
Information on eliminating the displayed errors:
è