background image

You can find information on troubleshooting in the event of incorrect behaviour in
the “Description of Automation system CPX-E” and the descriptions of the mod-
ules used 

è

 1.1 Applicable Documents.

9.2

Commissioning with CODESYS

CAUTION!

Risk of injury due to uncontrolled movements of the connected actuators.

Perform test runs of projects and applications without active actuators first.

For the configuration, parameterisation and programming of the product, use
CODESYS V3.

Requirements

PC (from Windows 7) with Ethernet interface

Components for network connection

Programming software CODESYS V3

Package CPX-E-CEC compliant with firmware of product

Preparations

The user requires administrator rights to install and operate programming soft-
wareCODESYS V3.

1. Install CODESYS V3.
2. CODESYS V3 with administrator rights.
3. Open Package Manager 

è

 menu command [Tools] [Package Manager].

4. Install current package for CPX-E-CEC 

è

 Online help for CODESYS V3

è

 Package Manager.

5. Restart CODESYS V3.
6. Connect the controller to the network connection [ETH1] or [ETH2] through a

switch/hub or directly to the PC 

è

 8.1 Network.

7. Adapt the network settings 

è

 menu command [Online] [Scan Festo devices]

è

 Online help for CODESYS V3 

è

 Scan Festo Devices.

The current version of the package CPX-E-CEC for CODESYS V3 is available in the
Festo Support Portal 

è

 www.festo.com/sp.

Further information is available in the product-specific Help

è

 Online help for CODESYS V3 

è

 Getting started.

Procedure for unwanted program states

If a program with real-time priority is not responding:
1. Set run/stop switch to stop.

Ä

The boot application cannot be started.

2. Restart the controller.
3. Establish connection to CPX-E-CEC.
4. Delete boot application using “Reset device to original state”

è

 General help for CODESYS V3.

9.3

Commissioning on Higher-order Controller

A device description file is available for the commissioning on a PROFINETIO mas-
ter system.

10

Service

NOTICE!

Accumulation of heat due to reduced air supply to electronics.

Keep the ventilation slots free and regularly remove contamination.

10.1

Firmware service (update)

Update the controller firmware with suitable software from Festo

è

 www.festo.com/sp.

11

Diagnostics and fault clearance

11.1

Diagnostics options

Various options are available for diagnosing errors:

Internal system diagnostics

LED indicators on the product

11.2

Internal system diagnostics

The internal system diagnostics is described in the “Description of automation
system CPX-E” 

è

 1.1 Applicable Documents.

11.3

LED Displays

The module- and network-specific LED displays are described below.
The system-specific LED indicators are described in the documents for the auto-
mation system CPX-E 

è

 1.1 Applicable Documents.

Module-specific LED indicators

Operation [Run]

LED
(green)

Meaning

Remedy

Lit

CODESYS application is running

Off

CODESYS application is not available or
has stopped

Tab. 11 Operation [Run]

Ethernet interfaces [LAETH1] [LAETH2]

LED
(green)

Meaning

Remedy

Lit

Network connection established
Status “Link”

Flashing

Network connection established
Status “Activity”

Off

No network connection

Check network connection.

Tab. 12 Ethernet interfaces [LAETH1] [LAETH2]

EtherCAT interface [LA EC]

LED
(green)

Meaning

Remedy

Lit

Network connection established
Status “Link”

Flashing

Network connection established
Status “Activity”

Off

No network connection

Check network connection.

Tab. 13 EtherCAT interface [LA EC]

Network-specific LED Displays

Network fault [NF]

LED
(red)

Meaning

Remedy

Network connection is not OK.
Possible causes:

Device name not correct

Check device name.

No connection to master

Switch on master.

Incorrect configuration

Correct MAC addresses for fieldbus inter-
face.

PROFINET IO controller defective

Repair controller.

Flashes

Network connection interrupted, short-cir-
cuited or disturbed

Check network connection.

Off

Network connection active, no network
error

Tab. 14 Network Fault [NF]

Connection status [XF1], [XF2]

LED
(green)

Meaning

Remedy

Lights up
green

PROFINET IO connection made
Status “Link”