You can find information on troubleshooting in the event of incorrect behaviour in
the “Description of Automation system CPX-E” and the descriptions of the mod-
ules used
è
9.2
Commissioning with CODESYS
CAUTION!
Risk of injury due to uncontrolled movements of the connected actuators.
•
Perform test runs of projects and applications without active actuators first.
•
For the configuration, parameterisation and programming of the product, use
CODESYS V3.
Requirements
–
PC (from Windows 7) with Ethernet interface
–
Components for network connection
–
Programming software CODESYS V3
–
Package CPX-E-CEC compliant with firmware of product
Preparations
The user requires administrator rights to install and operate programming soft-
wareCODESYS V3.
1. Install CODESYS V3.
2. CODESYS V3 with administrator rights.
3. Open Package Manager
è
menu command [Tools] [Package Manager].
4. Install current package for CPX-E-CEC
è
Online help for CODESYS V3
è
Package Manager.
5. Restart CODESYS V3.
6. Connect the controller to the network connection [ETH1] or [ETH2] through a
switch/hub or directly to the PC
è
7. Adapt the network settings
è
menu command [Online] [Scan Festo devices]
è
Online help for CODESYS V3
è
Scan Festo Devices.
The current version of the package CPX-E-CEC for CODESYS V3 is available in the
Festo Support Portal
è
Further information is available in the product-specific Help
è
Online help for CODESYS V3
è
Getting started.
Procedure for unwanted program states
If a program with real-time priority is not responding:
1. Set run/stop switch to stop.
Ä
The boot application cannot be started.
2. Restart the controller.
3. Establish connection to CPX-E-CEC.
4. Delete boot application using “Reset device to original state”
è
General help for CODESYS V3.
9.3
Commissioning on Higher-order Controller
A device description file is available for the commissioning on a PROFINETIO mas-
ter system.
10
Service
NOTICE!
Accumulation of heat due to reduced air supply to electronics.
•
Keep the ventilation slots free and regularly remove contamination.
10.1
Firmware service (update)
•
Update the controller firmware with suitable software from Festo
è
11
Diagnostics and fault clearance
11.1
Diagnostics options
Various options are available for diagnosing errors:
–
Internal system diagnostics
–
LED indicators on the product
11.2
Internal system diagnostics
The internal system diagnostics is described in the “Description of automation
system CPX-E”
è
11.3
LED Displays
The module- and network-specific LED displays are described below.
The system-specific LED indicators are described in the documents for the auto-
mation system CPX-E
è
Module-specific LED indicators
Operation [Run]
LED
(green)
Meaning
Remedy
Lit
CODESYS application is running
–
Off
CODESYS application is not available or
has stopped
–
Tab. 11 Operation [Run]
Ethernet interfaces [LAETH1] [LAETH2]
LED
(green)
Meaning
Remedy
Lit
Network connection established
Status “Link”
–
Flashing
Network connection established
Status “Activity”
–
Off
No network connection
Check network connection.
Tab. 12 Ethernet interfaces [LAETH1] [LAETH2]
EtherCAT interface [LA EC]
LED
(green)
Meaning
Remedy
Lit
Network connection established
Status “Link”
–
Flashing
Network connection established
Status “Activity”
–
Off
No network connection
Check network connection.
Tab. 13 EtherCAT interface [LA EC]
Network-specific LED Displays
Network fault [NF]
LED
(red)
Meaning
Remedy
Network connection is not OK.
Possible causes:
Device name not correct
Check device name.
No connection to master
Switch on master.
Incorrect configuration
Correct MAC addresses for fieldbus inter-
face.
PROFINET IO controller defective
Repair controller.
Flashes
Network connection interrupted, short-cir-
cuited or disturbed
Check network connection.
Off
Network connection active, no network
error
–
Tab. 14 Network Fault [NF]
Connection status [XF1], [XF2]
LED
(green)
Meaning
Remedy
Lights up
green
PROFINET IO connection made
Status “Link”
–