background image

Switch status

Function

Stop 

è

 run

A project that was stopped using the run/stop switch will be con-
tinued.

Tab. 5 Run/Stop Switch

5.2.3.2

Operator unit CDSB (optional)

The operator unit CDSB is available as an accessory

è

 www.festo.com/catalogue.

The functions of the operator unit are described in the “Description of controller
CPX-E-CEC-...-PN” 

è

 1.1 Applicable Documents.

5.2.4

Connecting Elements

5.2.4.1

Operating voltage supply

Port [XD]

1)

Signal

0

1

+24 V DC operating voltage supply U

EL/SEN

2

3

0 V DC operating voltage supply U

EL/SEN

1) The ports XD.0 and XD.1 and also XD.2 and XD.3, respectively, are interconnected in the terminal strip.

Tab. 6 Port [XD]

5.2.4.2

Network Connections

Port [XF1], [XF2], [ETH1], [ETH2],
[EC]

Signal

1

TD+

Transmitted data +

2

TD–

Transmitted data –

3

RD+

Received data +

4

n.c.

5

n.c.

6

RD–

Received data –

7

n.c.

8

n.c.

1)

Shield

Functional earth

1) Housing

Tab. 7 Port [XF1], [XF2], [ETH1], [ETH2], [EC]

Connection

Function

[XF1]

PROFINET IO Port 1

[XF2]

PROFINET IO Port 2

[ETH1]

[ETH2]

Ethernet interfaces for the connection of a programming
device, PC or operator unit CDPX

[EC]

EtherCAT Master

Tab. 8 Network Connections

The network connections ETH1 and ETH2 are connected to the controller via a
switch.

5.2.4.3

Memory card slot [Card]

The slot is used to save data and results to a memory card CAMC-M-MS-G32.

The data are saved in the directory /mnt/sdcard.

The data are accessed through SysFile and CAA.File 

è

 CODESYS libraries.

Requirements:

Maximum memory size: 32 GB

Formatting: FAT32 (one partition only)

When using a memory card, please note the direction and orientation.

Use only memory cards that are sold by Festo as accessories for the product

è

 www.festo.com/catalogue.

Festo does not provide any warranty for the use of other memory cards.

The memory card slot is only intended for user-monitored operation.

Do not use memory cards for continuous data recording.

Memory cards cannot be used to execute CODESYS boot projects.

5.2.4.4

USB interface [USB]

The USB interface (A-coded socket, USB specification 2.0) is used to save data
and results to external storage media.

The data from the USB memory are saved in the directory /mnt/usb.

The data are accessed through SysFile and CAA.File 

è

 CODESYS libraries.

Requirements:

Maximum memory size: 32 GB

Formatting: FAT32 (one partition only)

NOTICE!

Impermissible operating states of the controller result from high current con-
sumption at the USB interface.

Use only storage media with a current consumption of 

£

 0.5 A.

The USB interface is only intended for user-monitored operation.

Do not use storage media for continuous data recording.

USB storage devices cannot be used to execute CODESYS boot projects.

6

Transport and storage

Observe specifications for environmental and storage conditions

è

 13 Technical Data

è

 Tab. 19 Ambient Conditions UL/CSA.

7

Assembly

Assemble the module as outlined in the “Instruction manual for Automation
system CPX-E” 

è

 1.1 Applicable Documents.

8

Installation

8.1

Network

NOTICE!

Unauthorised Access to the Device Can Cause Damage or Malfunction.

When connecting the device to a network, protect the network from unauthor-
ised access.
Standards for security in information technology can be used for network pro-
tection measures, e.g. IEC 62443, ISO/IEC 27001.

Network

An access password only protects against unintentional modification.

NOTICE!

Transmission errors due to faulty installation or excessive transmission rates.

Please note the line specifications in the documentation of the controller.

8.2

Operating voltage supply U

EL/SEN

NOTICE!

Malfunction due to faulty installation.

Please note the information regarding the line specification, power supply
and earthing measures.

1. Please note the information in the “Instruction manual for Automation system

CPX-E” 

è

 1.1 Applicable Documents.

2. Make sure that the power supply is switched off.
3. Connect the lines to the terminal strip in accordance with the “Instruction

manual for Automation system CPX-E” 

è

 1.1 Applicable Documents. 

9

Commissioning

You can find information on commissioning the automation system CPX-E in the
“Instruction manual for automation system CPX-E”.
You can find information on the parameters in the “Description of
automation system CPX-E” and in the descriptions of the modules used

è

 1.1 Applicable Documents.

9.1

Behaviour of the Display Components after Error-free Commissioning

[NF] (red)

[XF1], [XF2] (green)

Off

Lights up or flashes

Tab. 9 Display Components after Error-free Commissioning

[PS] (green)

[PL] (green)

[SF] (red)

[M] (yellow)

Lights up

Lights up

Off

Off

Tab. 10 Display Components after Error-free Commissioning