Module status [MS]
LED
(green,
red,
orange)
Meaning
Remedy
Flashing
altern-
ately
red/green
The automation system CPX-E is in self-
test mode.
–
Lit up
orange
Bootloader
–
Off
No logic power supply to the network
interface
Check logic supply.
Tab. 15 Module status [MS]
Network status [NS]
LED
(green,
red,
orange)
Meaning
Remedy
Lit up
green
The automation system CPX-E is online
and has a network connection (normal
operating status).
–
Flashing
green
The automation system CPX-E is online
and has received an IP address but does
not have a configured network connection.
Check configuration of the automation
system CPX-E; it is possible that the auto-
mation system CPX-E is not assigned to a
master/scanner.
Lit up red
Communication has failed.
Non-permitted IP address set that is
already used in the network.
Correct IP address.
Flashing
red
One or more “I/O connections” are in the
“time-out state”.
Check the physical connection to the
master/scanner.
Flashing
altern-
ately
red/green
The automation system CPX-E is in self-
test mode.
–
Lit up
orange
Bootloader, if the LED [MS] is also lit up
orange
è
Network-specific LED indicators
–
Off
The automation system CPX-E is offline.
No IP address assigned or no IP address
received from DHCP server.
Check network connection.
Check IP addressing settings.
Tab. 16 Network status [NS]
12
Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations
è
www.festo.com/sp.
13
Technical data
General technical data
General technical data
Automation system CPX-E
Description of automation system CPX-E
è
1.1 Further applicable documents
Dimensions
(Length × width × height)
1)
[mm]
124.3 × 75.9 × 82.5
Product weight
2)
[g]
288
Mounting position
Vertical/horizontal
Ambient temperature
[°C]
–5 … +60 (–5 … +50)
3)
Storage temperature
[°C]
–20 … +70
Air humidity
(non-condensing)
[%]
0 … 95
Degree of protection in accordance with
EN 60529
IP20
Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)
through the use of PELV circuits
(protected extra-low voltage)
Electromagnetic compatibility
to EN 61000-6-2/-4 and NE 21
Module code/submodule code
CPX-E-CEC-C1-EP
222/102
CPX-E-CEC-M1-EP
222/103
Module identification
CPX-E-CEC-C1-EP
E-CEC-C1-EP
CPX-E-CEC-M1-EP
E-CEC-M1-EP
1) Including cover, not including linking element
2) Including linking element
3) for horizontal mounting position
Tab. 17 General technical data
Power supply
Operating voltage supply
U
EL/SEN
[V DC]
24
_
25
%
Intrinsic current consumption
at nominal operating voltage
24 V from U
EL/SEN
[mA]
typ. 150
Reverse polarity protection
24 V U
EL/SEN
against
0 V U
EL/SEN
Yes
Mains buffering time
[ms]
20
Tab. 18 Power supply
Network-specific data
Protocol
EtherNet/IP
1)
, EtherCAT
Transmission rate
[Mbps]
10/100 (full duplex/half duplex)
Crossover detection
Auto-MDI/MDI-X
Maximum cable length per
segment
[m]
100
2)
Cable specification
Cable type
Ethernet twisted pair cable, shielded
Transmission class
Category Cat 5/Cat 5e (link class)
Cable diameter
[mm]
6 … 8
Wire cross section
[mm
2
]
0.14 … 0.75; 22 AWG
3)
1) based on the Ethernet protocol IEEE 802.3
2) at a transmission rate of 100 Mbps
3) Required for maximum connection length between network participants
Tab. 19 Network-specific data