Requirements

PC (Windows 7 and later) with Ethernet interface

Components for network connection

Programming software CODESYS V3

Package CPX-E-CEC compliant with firmware of product

Preparations

The user requires administrator rights to install and operate programming soft-
wareCODESYS V3.

1. Install CODESYS V3.
2. Start CODESYS V3 with administrator rights.
3. Open Package Manager 

è

 menu command [Tools] [Package Manager].

4. Install the current package for CPX-E-CEC

è

  online help for CODESYS V3

è

 “Package Manager”.

5. Restart CODESYS V3 in order to use the new package.
6. Connect the controller to the network connection [ETH

1] or [ETH

2] through a

switch/hub or directly to the PC 

è

 8.1 Network.

7. Adapt the network settings 

è

 menu command [Online] [Scan Festo Devices]

è

 online help for CODESYS V3 

è

 “Scan Festo Devices”.

The current version of the package CPX-E-CEC for CODESYS V3 is available in the
Festo Support Portal 

è

 www.festo.com/sp.

Further information is available in the product-specific Help

è

 Online help for CODESYS V3 

è

 “Getting started”.

Procedure for unwanted program states

If a program with real-time priority is not responding:
1. Set run/stop switch to stop.

Ä

The boot application cannot be started.

2. Restart the controller.
3. Establish connection to CPX-E-CEC.
4. Delete boot application using “Reset device to original state”

è

 General help for CODESYS V3.

10

Service

NOTICE!

Accumulation of heat due to reduced air supply to electronics.

Keep the ventilation slots free and regularly remove contamination.

10.1

Firmware service (update)

Update the controller firmware with suitable software from Festo

è

 www.festo.com/sp.

11

Diagnostics and fault clearance

11.1

Diagnostics options

Various options are available for diagnosing errors:

Internal system diagnostics

LED indicators on the product

11.2

Internal system diagnostics

The internal system diagnostics is described in the “Description of automation
system CPX-E” 

è

 1.1 Further applicable documents.

11.3

LED indicators

The module- and network-specific LED displays are described below.
The system-specific LED indicators are described in the documents for the auto-
mation system CPX-E 

è

 1.1 Further applicable documents.

Module-specific LED indicators

Operation [Run]

LED
(green)

Meaning

Remedy

Lit

CODESYS application is running

Off

CODESYS application is not available or
has stopped

Tab. 11 Operation [Run]

Ethernet interfaces [LA

ETH

1] [LA

ETH

2]

LED
(green)

Meaning

Remedy

Lit

Network connection established
Status “Link”

Flashing

Network connection established
Status “Activity”

Off

No network connection

Check network connection.

Tab. 12 Ethernet interfaces [LA

ETH

1] [LA

ETH

2]

EtherCAT interface [LA EC]

LED
(green)

Meaning

Remedy

Lit

Network connection established
Status “Link”

Flashing

Network connection established
Status “Activity”

Off

No network connection

Check network connection.

Tab. 13 EtherCAT interface [LA EC]

Network-specific LED indicators

Connection status [XF1], [XF2]

LED
(green)

Meaning

Remedy

Lit

Network connection established
Status “Link”

Flashing

Network connection established
Status “Activity”

Off

No network connection

Check network connection.

Tab. 14 Connection status [XF1], [XF2]

Module status [MS]

LED
(green,
red,
orange)

Meaning

Remedy

Lit up
green

Normal operating status

Flashing
green

Configuration of automation system CPX-E
not complete or not correct

Complete or correct configuration of the
automation system CPX-E.

Lit up red

Error cannot be rectified

Contact Festo Service 

è

 www.festo.com.

Flashing
red

Error can be rectified

Check configuration of the automation
system CPX-E.