8
Festo — CPX-AP-A-8DO-M12-5P — 2022-07
Parameterisation
Response of the display components of the module after error-free commissioning
[MD]
[PL]
green light
green light
Tab. 5: Response of the LED displays of the module after error-free commissioning
Information on troubleshooting in the event of incorrect response:
9 Diagnostics and fault clearance
8
Parameterisation
Various parameters are available for reading out information about the modules in an automation
system CPX-AP-A and for adapting the modules to the application situation.
Write access to the parameters is typically performed by the higher-level controller using the device
descriptions specific to the host system.
ID
Parameter
Instances Data type
Access
1
)
Array
size
246
Fieldbus serial number
1
UINT32
ro
–
791
Product key
1
CHAR
ro
12
960
Firmware version
1
CHAR
ro
30
20000
Module code
1
UINT32
ro
–
20010
AP-ASIC hardware version
1
UINT16
ro
–
20011
libAP version
1
CHAR
ro
30
20022
Configuration of load supply voltage moni-
toring (PL)
1
ENUM_ID
rw
–
20052
Response in the error state
1
ENUM_ID
rw
–
20069
CRC error counter
3
UINT16
ro
–
20070
Incorrect AP slot count
3
UINT16
ro
–
20081
Mask for forcing the outputs
1
UINT8
rw
–
20082
State of the outputs to be forced
1
UINT8
rw
1
20083
Force LED states
1
UINT16
rw
1
20085
Measured value of temperature AP-ASIC [°C] 1
INT16
ro
–
20087
Current measured value of logic supply (PS) 1
UINT16
ro
–
20088
Current measured value of load supply (PL)
1
UINT16
ro
–
20089
Quality of the transmission line
3
UINT16
ro
17