background image

Index

A

Actuators

connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2-6

C

CP module

replace during operation . . . . . . . . . . . . . . . . . .  2-19

D

Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  IV

F

Fitting

input module . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-5
output module . . . . . . . . . . . . . . . . . . . . . . . . . . .  2-4

I

Information on this manual . . . . . . . . . . . . . . . . . . . .  VII
Input module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-25

circuitry examples of CP-E16-M12x2-... . . . . . .  1-15
circuitry examples of CP-E16-M8 . . . . . . . . . . .  1-13
circuitry examples of CP-E16N-M12x2 . . . . . . .  1-19
circuitry examples of CP-E16N-M8 . . . . . . . . . .  1-17
connect to node . . . . . . . . . . . . . . . . . . . . . . . . .  1-20
fitting on a wall. . . . . . . . . . . . . . . . . . . . . . . . . . .  1-5
fitting onto a hat rail . . . . . . . . . . . . . . . . . . . . . . .  1-6
internal layout of CP-E16-M12x2-... . . . . . . . . .  1-14
internal layout of CP-E16-M8 . . . . . . . . . . . . . .  1-12
internal layout of CP-E16N-M12x2 . . . . . . . . . .  1-18
internal layout of CP-E16N-M8 . . . . . . . . . . . . .  1-16

A. Index

CP..EA  9901b

A-3

Содержание CP-A08 Series

Страница 1: ...Compact Performance CP Modules Electronics Input modules type CP E16 M Output modules type CP A08 M12...

Страница 2: ...ng distribution and utilization of this docu ment as well as the communication of its contents to others without expressed authorization is prohibited Offenders will be held liable for the payment of...

Страница 3: ...Part no 165 225 Title Manual Designation P BE CPEA GB II CP EA 9901b...

Страница 4: ...allation 1 8 1 3 1 Connecting sensors 1 9 1 3 2 Connecting the input module 1 20 1 4 Instructions on commissioning 1 22 1 5 Technical specifications 1 26 2 Output module type CP A08 M12 2 1 Overview 2...

Страница 5: ...on If used in conjunction with commercially available com ponents such as sensors and actuators the specified limit values for pressures temperatures electrical data torques etc must be observed Pleas...

Страница 6: ...correctly These instructions are always printed in italics are framed and also signalled by pictograms Danger categories A distinction is made between the following WARNING This means that personal i...

Страница 7: ...High voltages or undefined switching states of the elec tronic components which may influence connected cir cuits Electrostatically vulnerable components These will be damaged if you touch the contact...

Страница 8: ...information on the method of operation fitting installation and com missioning of the following CP modules This manual refers to Input modules PNP CP E16 M8 CP E16 M12x2 CP E16 M12x2 5POL NPN CP E16N...

Страница 9: ...valve terminal pneumatics type P BE CPV or type P BE CPA CP modules electronics Contents Special information on commissioning programming and diagnosing related to the node used Information on fittin...

Страница 10: ...es service unit measuring system cylinders or linear drives Contents Installation commissioning and diagnosis with the SPC200 Standard components and modules Functions of the WinPISA software package...

Страница 11: ...X CP EA 9901b...

Страница 12: ...Chapter 1 Input module type CP E16 M 1 Input module type CP E16 M CP E16 M 9901b 1 1...

Страница 13: ...E16 M 1 3 1 1 1 Display and connecting elements 1 4 1 2 Fitting 1 5 1 3 Installation 1 8 1 3 1 Connecting sensors 1 9 1 3 2 Connecting the input module 1 20 1 4 Instructions on commissioning 1 22 1 5...

Страница 14: ...owing types Type Explanation CP E16 M12X2 CP E16N M12X2 Provides 16 PNP inputs sensor connections via 8 sockets with M12 thread Provides 16 NPN inputs sensor connections via 8 sockets with M12 thread...

Страница 15: ...on for input type INPUT P for PNP inputs INPUT N for NPN inputs Sensor connections Green LED for status display one LED per input 4 5 6 7 8 9 Status LED green CP connection Protective cap Groove for i...

Страница 16: ...ace area CP E16 M8 approx 150 mm x 66 mm CP E16 M12x2 approx 141 mm x 78 mm The diagram below shows the dimensions of the four threaded holes of screw size M4 Fitting on a wall 1 2 Input module type C...

Страница 17: ...an support the weight of the module 2 Fit a hat rail support rail EN 50022 35x15 width 35 mm height 15 mm 3 Fasten the hat rail at least every 100 mm to the sup port surface 4 Let both fastenings on t...

Страница 18: ...order to remove the module from a hat rail proceed as follows 1 Loosen the screws 2 Remove the housing 3 Use a screwdriver to prize open the hat rail and remove the module 1 2 Fastening Screwdriver F...

Страница 19: ...plied load voltage You thereby avoid unintentional movements of the connected actuators undefined switching states of the electronic components WARNING Connect the earth cable on the side of the housi...

Страница 20: ...th thread M12x1 CP E16 M8 Use the plug with union nut with thread M8x1 outer diameter max 12 mm KM8 M8 GSGD Fasten the plugs with the aid of the union nuts in order to avoid unintentional loosening e...

Страница 21: ...ig 1 5 Pin assignment of input module type CP E16 M8 E Input Fig 1 6 Pin assignment of input module type CP E16 M12x2 Ex 3 Ex Ex 2 Pin 3 0V Pin 4 Ex Pin 1 24V Pin 1 24V Pin 4 Ex 2 Pin 3 0V Pin 2 Ex 3...

Страница 22: ...onnection Fig 1 7 Pin assignment of input module type CP E16 M12x2 5POL Ex 3 Ex Ex 2 Pin 3 0V Pin 4 Ex Pin 1 24V Pin 1 24V Pin 4 Ex 2 Pin 3 0V Pin 2 Ex 3 Ex 1 Pin 2 Ex 1 1 1 1 Input module type CP E16...

Страница 23: ...6 M8 PNP inputs 1 2 3 PLC I PC Ex e g via field bus Logic recognition Ex Green LED Ex Fig 1 8 Internal layout of input module CP E16 M8 24 V 10 15 2 Pin 1 Pin 2 Pin 3 3 1 0 V 1 Input module type CP E1...

Страница 24: ...inputs Pin assignment Circuitry examples 1 2 3 Three wire sensor Two wire sensor Contact E Input Fig 1 9 Circuitry examples of input module CP E16 M8 Pin 1 24 V Pin 3 0 V Pin 2 Ex 2 3 1 1 Input modul...

Страница 25: ...1 Green LED Ex 1 4 5 6 7 PLC I PC Ex e g via field bus Logic recognition Ex Green LED Ex Pin 5 only with type CP E16 M12x2 5POL Earth connection Fig 1 10 Internal layout of input module CP E16 M12x2...

Страница 26: ...1 2 3 4 Pin 5 only with type CP E16 M12x2 5POL Earth connection 2 way distributor T piece Sensor 2 Ex 1 Sensor 1 Ex E Input Fig 1 11 Circuitry examples of input module CP E16 M12x2 3 4 2 Pin 1 24 V P...

Страница 27: ...N M8 NPN inputs 1 2 3 PLC I PC Ex e g via field bus Logic recognition Ex Green LED Ex Fig 1 12 Internal layout of input module CP E16N M8 24 V 10 15 2 Pin 3 Pin 2 Pin 1 3 1 0 V 1 Input module type CP...

Страница 28: ...nt Circuitry examples 1 2 3 Three wire sensor negative switching Two wire sensor negative switching Contact E Input Fig 1 13 Circuitry examples of input module CP E16N M8 Pin 1 24 V Pin 3 0 V Pin 2 Ex...

Страница 29: ...field bus Logic recognition Ex 1 Green LED Ex 1 4 5 6 PLC I PC Ex e g via field bus Logic recognition Ex Green LED Ex Fig 1 14 Internal layout of input module CP E16N M12x2 24 V 10 15 Pin 3 Pin 2 5 3...

Страница 30: ...try examples 1 2 3 2 way connector T piece Sensor 2 Ex 1 negative switching Sensor 1 Ex negative switching E Input Fig 1 15 Circuitry examples of input module CP E16N M12x2 1 2 3 Pin 1 24 V Pin 4 Ex P...

Страница 31: ...o Max permitted string length Cable type Field bus node with CP connection 10 m KVI CP 1 or KVI CP 2 can be used as drag chain Axis interface type SPC AIF See manual for SPC200 type P BE SPC200 Powerb...

Страница 32: ...ction of the higher order system field bus node axis interface or Powerbox the CP connection of an output module the CP connection of a valve terminal Further instructions can be found in the appropri...

Страница 33: ...bus node the new string assignment must be saved if it has been modified CP modules added or removed To do this press the SAVE button on the node Proceed as described in the manual CP system installa...

Страница 34: ...short circuit in sensor supply or In conjunction with CP node incorrect string assignment when voltage is switched on In conjunction with the SPC200 see user manual for the SPC200 None or Eliminate s...

Страница 35: ...pply In conjunction with the CP field bus node Disconnect the input module briefly from the line or switch off the power supply at the node and then switch it on again In conjunction with the SPC200 P...

Страница 36: ...1 signal and if there is a line assignment error PLEASE NOTE In conjunction with the CP field bus node If there is a line assignment error during the switch on phase the CP node will switch the power...

Страница 37: ...ra Low Voltage Electromagnetic compatibility interference emission resistance to interference Tested as per EN 55011 limit value class B Tested as per EN 50082 2 Digital inputs Design 16 inputs as per...

Страница 38: ...PELV power unit Protected Extra Low Voltage Electromagnetic compatibility interference emission resistance to interference Tested as per EN 55011 limit value class B Tested as per EN 50082 2 Digital i...

Страница 39: ...1 Input module type CP E16 M 1 28 CP E16 M 9901b...

Страница 40: ...Chapter 2 Output module type CP A08 M12 2 Output module type CP A08 M12 CP A08 M12 9901b 2 1...

Страница 41: ...g 2 4 2 3 Installation 2 5 2 3 1 Connecting the actuators 2 6 2 3 2 Connecting the output module 2 13 2 3 3 Connecting the load voltage 2 14 2 4 Instructions on commissioning 2 17 2 5 Technical specif...

Страница 42: ...utput module 1 2 3 4 Designation for output type OUTPUT P for PNP outputs OUTPUT N for NPN outputs CP connection Connections for actuators Yellow LED for status display one LED per output 5 6 7 8 9 0...

Страница 43: ...ram below shows the dimensions for the four threaded holes for the M4 screws Fitting on a wall Fig 2 2 Fitting dimensions for output module CP A08 M12 Fitting onto a hat rail is undertaken in exactly...

Страница 44: ...wer supply to all the output modules You thereby avoid unintentional movements of the connected actuators undefined switching states of the electronic components WARNING Connect the earth cable on the...

Страница 45: ...Seal the unused sensor connections with the protective caps supplied Only then is compliance with class of protection IP65 ensured Pin assignment of the actuator connections CP A08 M12 PNP outputs n c...

Страница 46: ...t module type CP A08 M12 5POL 1 2 Pin 5 Earth connection Internal connection in the module A Output n c not connected Fig 2 4 Pin assignment of output module CP A08 M12 5POL Ax 1 Pin 3 0V Pin 4 Ax Pin...

Страница 47: ...n 0 2 4 6 Ax 1 connection 1 3 5 7 not connected 5 6 7 8 9 Yellow LED Green LED Diagnosis short circuit overload load voltage failure Actuator connection Pin 5 only with type CP A08 M12 5POL Earth conn...

Страница 48: ...08 M12 5POL Earth connection With type CP A08 M12 not connected With type CP A08 M12 5POL connection 0 2 4 6 Ax 1 connection 1 3 5 7 not connected 3 4 5 Example 1 Example 2 Not permitted Fig 2 6 Circu...

Страница 49: ...n Consuming device load must be supplied via this 24 V connection n c not connected A Output Fig 2 7 Pin assignment of output module CP A08N M12 Ax 1 Ax Pin 2 1 Pin 2 1 Pin 3 n c Pin 3 n c Pin 4 Ax Pi...

Страница 50: ...cal isolation Not connected 5 6 7 8 Yellow LED Green LED Diagnosis short circuit overload load voltage failure Actuator connection Fig 2 8 Internal layout of output module CP A08N M12 Pin 3 Pin 4 Pin...

Страница 51: ...connection Example 1 Example 2 Not permitted A Output n c not connected Consuming device load must be supplied via this 24 V connection Fig 2 9 Circuitry examples of output module CP A08N M12 Pin 1 2...

Страница 52: ...P 1 or KVI CP 2 can be used as drag chain Axis interface type SPC AIF See manual for the SPC200 type P BE SPC200 Powerbox Type CP FB TBOX See manual for the higher order system Communication takes pla...

Страница 53: ...otection against electric shock protection against direct and indirect contact in accordance with EN 60204 1 IEC 204 is guaranteed on Festo valve terminals Safety transformers with the adjacent design...

Страница 54: ...ed 1 2 3 Earth connection pin 4 Earth connection on side of housing Load voltage can be switched off separately the operating voltage is supplied via the CP connection Fig 2 10 Pin assignment of load...

Страница 55: ...output module and the earth connection at pin 4 have the same potential and that there are no equalizing currents You can then avoid interference caused by electromag netic influences PLEASE NOTE Che...

Страница 56: ...string assignment must be saved if it has been modified CP modules added or removed To do this press the SAVE button on the node Proceed here as described in the manual CP system installation and com...

Страница 57: ...or In conjunction with the CP node incorrect string assignment when power supply is switched on In conjunction with the SPC200 see user manual for the SPC200 None or eliminate short circuit overload...

Страница 58: ...can replace the module by another of the same type during operation Replacing the CP module PLEASE NOTE Observe here the instructions in the manual for the higher order system e g CP system CP field b...

Страница 59: ...oltage Electromagnetic compatibility interference emission resistance to interference Tested as per EN 55011 limit value class B Tested as per EN 50082 2 Load voltage connection rated value protected...

Страница 60: ...mpatibility interference emission resistance to interference Tested as per EN 55011 limit value class A Tested as per EN 50082 2 Load voltage connection rated value protected against incorrect polarit...

Страница 61: ...2 Output module type CP A08 M12 2 22 CP A08 M12 9901b...

Страница 62: ...Appendix A Index A Index CP EA 9901b A 1...

Страница 63: ...A Index A 2 CP EA 9901b...

Страница 64: ...rcuitry examples of CP E16 M12x2 1 15 circuitry examples of CP E16 M8 1 13 circuitry examples of CP E16N M12x2 1 19 circuitry examples of CP E16N M8 1 17 connect to node 1 20 fitting on a wall 1 5 fit...

Страница 65: ...CP A08N M12 2 12 fitting on a hat rail 2 4 fitting on a wall 2 4 internal layout of CP A08 M12 2 8 internal layout of CP A08N M12 2 11 P Pictograms VI Pin assignment inputs 1 10 NPN output 2 10 opera...

Страница 66: ...input module 1 22 output module 2 17 T Target group V Technical specifications input module CP E16 M PNP 1 26 input module CP E16N M NPN 1 27 output module CP A08 M12 PNP 2 20 output module CP A08N M...

Страница 67: ...A Index A 6 CP EA 9901b...

Отзывы: