1.3.2 Connecting the input module
WARNING
Please observe the maximum permitted string
lengths in each case. You will then avoid faults in
data exchange between the input module and the
higher-order system (e.g. the field bus node).
Use only the following cables for connecting the
modules:
For connection to
Max. permitted
string length
Cable type
Field bus node
with CP connection
10 m
- KVI-CP-1-...
or
- KVI-CP-2-...
(can be used as
drag chain)
Axis interface
type SPC-AIF-...
See manual for
SPC200 type
P.BE-SPC200-...
Powerbox
type CP-FB-TBOX-
...
See manual for
higher-order
system
By means of the CP cable the module is supplied with
the following:
– operating voltage for the internal electronic compo-
nents
– operating voltage for the connected sensors
– connection for data exchange.
1. Input module type CP-E16...-M...-...
1-20
CP-E16...-M... 9901b
Содержание CP-A08 Series
Страница 1: ...Compact Performance CP Modules Electronics Input modules type CP E16 M Output modules type CP A08 M12...
Страница 3: ...Part no 165 225 Title Manual Designation P BE CPEA GB II CP EA 9901b...
Страница 11: ...X CP EA 9901b...
Страница 12: ...Chapter 1 Input module type CP E16 M 1 Input module type CP E16 M CP E16 M 9901b 1 1...
Страница 39: ...1 Input module type CP E16 M 1 28 CP E16 M 9901b...
Страница 40: ...Chapter 2 Output module type CP A08 M12 2 Output module type CP A08 M12 CP A08 M12 9901b 2 1...
Страница 61: ...2 Output module type CP A08 M12 2 22 CP A08 M12 9901b...
Страница 62: ...Appendix A Index A Index CP EA 9901b A 1...
Страница 63: ...A Index A 2 CP EA 9901b...
Страница 67: ...A Index A 6 CP EA 9901b...