A
Technical appendix
36
Festo – GDCP-CMMP-AS-M0-S1-EN – 1412a – English
A.1.2
General, operating and environmental conditions CMMP-AS-...-M0
The technical data for the CMMP-AS-...-M0 can be found in its entirety in the hardware
documentation GDCP-CMMP-M0-HW-...
General technical data
Approvals
CE marking (see declaration of
conformity)
In accordance with EC Machinery Directive
In accordance with EU Low Voltage Directive
In accordance with EU EMC directive
The device is intended for use in an industrial environment. Meas
ures for interference suppression may need to be implemented in
residential areas.
Tab. A.3
Technical data, general
Operating and environmental conditions
Permissible setup altitude above sea level
with rated output
[m]
1000
with power reduction
[m]
1000 … 2000
Air humidity
[%]
0 … 90 (non-condensing)
Protection class
IP20
Degree of contamination in
accordance with EN 61800-5-1
2
The integrated safety equipment requires compliance with degree
of contamination 2 and thus a protected fitting space (IP54). This
must always be ensured through appropriate measures, e. g.
through installation in a control cabinet.
Operating temperature
[°C]
0 … +40
Operating temperature
with power reduction of
2.5 % per Kelvin
[°C]
+40 … +50
Storage temperature
[°C]
-25 … +70
Vibration and shock resistance
Operation
in accordance with EN 61800-5-1, section 5.2.6.4
Transport
in accordance with EN 61800-2, section 4.3.3
Tab. A.4
Technical data: Operating and environmental conditions