MONITORING SYSTEM
3. Menu structure
The menu in the system features a tree structure based on four different levels.
The values that the controller shows on the display during the normal operating mode are identified in
level 0
, i.e.
the thermoregulation temperature (temperature detected by probe “
t01
” on the exchanger inlet) or an alarm code.
The menu where the seven labels are displayed (titles) is accessed in
livello 1
.
The menus in
level 2
and, successively, in
level 3
, contain a sub-menu or the values in the open menu item.
Lastly,
level 4
contains parameter menu values only.
The diagram below illustrates the structure of the menu with all the parameters that form it.
LEVEL 0
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
Probe value t01
or Alarm active
Cooling set
label
Cooling set
value
Heating set
label
Heating set
value
Analogue inputs
Code Description of input
Input status
Enter password
Parameter index
N hours
Parameter value
Value
H2O input probe
H2O output probe
Condensation probe
Active alarms code
Description of input
High pressure switch
Low pressure switch
Water side safety
ON-OFF Remoto
HEAT-COOL Remoto
Description of par.
Config. par.
Compressor par.
Fan Par.
Alarm par.
Pump par.
Anti-freeze par.
Defrost par.
Description of par.
Compressor hours
Pump hours
See errors table
Code
Code
Code
Alarms
Digital inputs
Parameters
Password
Password value
Hour counter
Set point
..
..
..
..
..
..
..