14
TECHNICAL DATA AND PERFORMANCES
Frame
1
2
Model
19 .1
22 .1
26 .1
30 .1
35 .1
40 .1
U.M.
Power supply
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
V-ph-Hz
NOMINAL performances - Low noise setting up (AS) - Radiant plants
IR
Cooling A35W18
( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity
23,7
26,2
30,7
36,7
42,4
47,7
kW
Power input
7,62
8,41
9,79
12,0
13,8
15,6
kW
EER
3,11
3,12
3,14
3,06
3,07
3,06
-
Water flow rate plant side
4087
4534
5307
6354
7333
8261
l/h
Pressure drops plant side
36
43
36
50
43
54
kPa
IP
Cooling A35W18
( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity
23,2
25,7
30,1
35,9
41,5
46,7
kW
Power input
7,55
8,32
9,69
11,9
13,7
15,5
kW
EER
3,07
3,09
3,11
3,02
3,03
3,01
-
Water flow rate plant side
4002
4448
5204
6217
7179
8089
l/h
Pressure drops plant side
34
42
34
48
41
51
kPa
Heating A7W35
( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity
20,3
22,6
26,3
31,6
36,5
41,2
kW
Power input
5,24
5,77
6,73
8,34
9,49
10,9
kW
COP
3,87
3,92
3,91
3,79
3,85
3,78
-
Water flow rate plant side
3463
3857
4491
5383
6223
7011
l/h
Pressure drops plant side
26
32
26
37
31
39
kPa
Heating A2W35
( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity
16,8
18,8
21,8
26,2
30,2
34,0
kW
Power input
5,16
5,67
6,61
8,19
9,32
10,6
kW
COP
3,26
3,32
3,30
3,20
3,24
3,21
-
Water flow rate plant side
2880
3206
3720
4474
5160
5811
l/h
Pressure drops plant side
18
22
18
26
22
27
kPa
Data declared according to
EN 14511
. The values are referred to units without options and accessories.