11
TECHNICAL DATA AND PERFORMANCES
Frame
1
2
Model
19 .1
22 .1
26 .1
30 .1
35 .1
40 .1
U.M.
Power supply
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
V-ph-Hz
NOMINAL performances - Base setting up (VB) - Standard plants
Frame
1
2
Model
19 .1
22 .1
26 .1
30 .1
35 .1
40 .1
U.M.
Power supply
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
V-ph-Hz
NOMINAL performances - Base setting up (VB) - Standard plants - EUROVENT certified data
Data declared according to
EN 14511
. The values are referred to units without options and accessories.
IR
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
19,9
22,1
25,8
30,8
35,6
40,2
kW
Power input
6,82
7,50
8,76
10,8
12,3
13,9
kW
EER
2,92
2,95
2,95
2,85
2,89
2,89
-
Water flow rate plant side
3432
3809
4444
5319
6143
6932
l/h
Pressure drops plant side
26
31
26
36
31
38
kPa
IP
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
19,5
21,7
25,3
30,2
34,9
39,4
kW
Power input
6,75
7,42
8,66
10,7
12,2
13,8
kW
EER
2,89
2,92
2,92
2,82
2,86
2,86
-
Water flow rate plant side
3363
3741
4358
5216
6023
6795
l/h
Pressure drops plant side
25
30
25
35
29
37
kPa
Heating A7W45
( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
21,0
23,3
27,1
32,5
37,6
42,4
kW
Power input
6,49
7,14
8,33
10,3
11,7
13,4
kW
COP
3,24
3,26
3,25
3,16
3,21
3,16
-
Water flow rate plant side
3568
3961
4610
5515
6386
7188
l/h
Pressure drops plant side
27
33
27
38
33
41
kPa
Heating A2W45
( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
17,4
19,3
22,5
26,8
31,0
35,0
kW
Power input
6,40
7,03
8,21
10,1
11,5
13,2
kW
COP
2,72
2,75
2,74
2,65
2,70
2,65
-
Water flow rate plant side
2954
3278
3825
4559
5276
5942
l/h
Pressure drops plant side
19
23
19
27
23
28
kPa
IR
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
20,0
22,2
25,9
31,0
35,8
40,4
kW
EER
2,97
3,00
2,99
2,92
2,96
2,95
-
Pressure drops plant side
26
31
25
36
30
38
kPa
ESEER
3,36
3,39
3,38
3,30
3,34
3,33
-
IP
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
19,6
21,8
25,4
30,4
35,1
39,6
kW
EER
2,94
2,98
2,97
2,90
2,93
2,91
-
Pressure drops plant side
25
30
25
34
29
37
kPa
ESEER
3,32
3,37
3,36
3,28
3,31
3,29
-
Heating A7W45
(air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity
20,9
23,2
27,0
32,3
37,4
42,1
kW
COP
3,27
3,30
3,29
3,20
3,25
3,21
-
Pressure drops plant side
28
34
27
39
33
41
kPa
Содержание RMA series
Страница 40: ...40...
Страница 41: ...41 DECLARATION OF CONFORMITY...
Страница 42: ...42...
Страница 43: ...43...