11
INSTALLATION
WEIGHT OF THE UNITS
HOW TO INSTALL INDOOR UNITS
• These indoor unit models can be ceiling mounted using 4 tie-rods.
Choose the most suitable fixing method considering the structure
of the ceiling and the weight of the unit as shown in the table.
• Make sure that the condensation drain pipe slants in the correct
way. Use the nuts and check nuts to adjust the four bearing points
in height.
• Definitively tighten the nuts and check nuts on to the tie rods so as
to prevent vibrations that could impair the stability of the unit
MOD.
12000
18000
24000
30000
30000-3
36000
36000-3 48000-3
Weight of the indoor unit (Kg)
21
36
38
38
58
58
58
58
Weight of the outdoor unit (Kg)
36
53
56
81
85
93
93
105
INSTALLATION SITE OF THE INDOOR UNIT
Comply with the following recommendations when choosing the
installation site for the interior unit:
• Position it in a place that is able to bear it and where vibrations and
noise cannot be amplified.
• Position it away from heat and steam sources and where air intake
and delivery are not obstructed.
• Position the unit so that its pipes can be easily connected to the
exterior unit.
• Position it in a point where the treated air can be distributed all over
the room.
• Do not install the unit in places where there is inflammable gas or
acid or alkaline substances that could damage the heat exchan-
gers in copper-aluminium, or the plastic components.
• Position the unit so that its front part is free from obstructions.
• When the unit is installed in a false ceiling, remember to make an
inspection door so that the electrical parts can be inspected and
serviced.
• If the air is distributed with conventional channels, insert vibration-
dampening joints between the delivery and the channel itself.
• Comply with the minimum space for installation and maintenance
indicated in
Fig.1.
>15cm
>10cm
>10cm
>10cm
>30cm
>30cm
Fig.1
Fig.2
Содержание midas pc10