GENERAL SPECIFICATIONS
AVAILABLE ACCESSORIES
The following accessories are available for this category:
- Control and Monitoring Panels
A set of panels is available for remote wall installation formed by three different types of control: commutator,
basic thermostat and evolved thermostat.
- 3-way valve (obligatory for operation in the cooling mode)
The three-way valve is not only required to control the ambient temperature, but also to block the flow of
chilled water to the coil if the level of condensed water in the tray should rise in an abnormal way.
It is obligatory to install this valve if the unit is used for operation in the Cooling mode during summer as this
stops it from cooling too much during the periods when the fan remains at a standstill, thus preventing the
unpleasant formation of condensation on the casing of the machine.
- Enabling thermostat (TC-F)
This accessory can be used with the “commutator” control panel to inhibit fan operation in the heating mode if
the temperature of the coil fails to reach an acceptable operating value.
ACCESSORY COMBINATIONS
VERSION
UNIT WITH 2 PIPES
UNIT WITH 4 PIPES
ACCESSORY
04
08
10
12
16
20
04-4T 10-4T 20-4T
CONTROL
CMR-F
•
•
•
•
•
•
TAR-F
•
•
•
•
•
•
TER-F
•
•
•
3-WAY VALVE
VTV 1 - B
•
•
•
•
•
VTV 2 - B
•
•
•
•
VTV 3 - B
(1)
•
•
VTV 2 - B
(1)
•
ENABLING
THERMOSTAT
TC-F (NB)
•
•
•
•
•
•
(1): 3-way valve for the Secondary Coil in the version with 4 pipes.
(NOTE): Can only be used in conjunction with the Remote Control (CMR-F).