25
ECONCEPT 100
4.3 Technical data table
Powers
Pmax
Pmin
Heat Output (Lower Heating Power - Hi)
kW
92,0
13,8
Useful Heat Output 80°C - 60°C
kW
90,4
13,6
Useful Heat Output 50°C - 30°C
kW
96,8
14,4
Gas supply
Pmax
Pmin
Gas nozzles G20
mm
6,70
Supply pressure G20
mbar
20,0
Delivery G20
nm3/h
9,72
1,46
Gas nozzles G31
mm
4,75
Supply pressure G31
mbar
37,0
Delivery G31
kg/h
7,2
1,8
Air nozzle
mm Ø
23,5
Heating
Max. working pressure in heating
bar
6
Min. working pressure in heating
bar
0,8
Boiler water content
litres
13
Dimensions, weights connections
Height
mm
1650
Width
mm
700
Depth
mm
400
Weight with packing
kg
165
Gas system connection
DN50
Heating system delivery
DN80
Heating system return
DN80
Electrical power supply
Max. electrical power absorbed
W
300
Power supply voltage/frequency
V/Hz
230/50
Electrical protection rating
IP
X5D