DOMINA 80 E
60
Chart 6
Check D.H.W. and C.H. modulation
Does burner
flame modulate?
Check wiring connection
to CH sensor
Normal operation
carry out
YES
NO
Check CH sensor
and replace it if necessary
Check voltage across
terminals X10-1 / X10-2
of main board (0-6V DC)
Boiler operated
on central heating mode
Does burner
flame modulate?
Check wiring connection
to DHW sensor
Normal operation
carry out
YES
NO
Check DHW sensor
and replace it if necessary
Check voltage across
terminals X10-1 / X10-2
of main board (0-6V DC)
Boiler operated
on DHW mode