-46-
Door Lock Controlled with Dry Contact
1.The external power supply must be used according
to the lock.
2.The inside relay contact is restricted to 230Vac 1A or
24Vdc 1A.
3.The jumper must be taken off before connecting.
4.Setup the
Unlock Mode
according to different lock
types.
•
Power-on-to-unlock type:Unlock
Mode=0 (by default)
•
Power-off-to-unlock type:Unlock
Mode=1
Take off the jumper
1 2 3
L1 L2 PL S+ S-
LOCK
POWER
SUPPLY
* DT-RLC relay actuator is needed for 2nd lock connection.
Connecting Electric Lock
Door Lock Controlled with Internal Power
1.Electronic lock of Power-on-to-unlock
type should be used.
2.The door lock is limited to 12V, and
holding current must be less than 250mA.
3.The jumper should be placed on position
2 and 3 before connecting.
4.The door lock control is not timed from
Exit Button(EB).
5.The
Unlock Mode
must be set to 0 (by
default).
EB
*
LOCK
Jumper position on 2&3
1 2 3
L1 L2 PL S+ S-