FEMA ELECTRÓNICA . Series S . S40-C1

14

1.19 Configuration menu (cont.)

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 

not apply to instrument restart due to change in configuration.

• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func

-

tion. During this waiting time, the display shows all decimal points 

on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui

-

sition and there is no communications or control being performed. 

After  the  configured  time  is  over,  the  instrument  starts  in  normal 

function. Delay value between 0 and 200 seconds.
•  the  ‘

Reset

’  (‘

rSt

’)

 

parameter  will  execute  a  reset  of  the  counter 

each time the instrument is restarted.

1.19.15 Menu ‘On Power Up’

Tools

Key UP

 

(‘fast access’)

Memory of 

maximum

Memory of 

minimum

Setpoint 1

Setpoint 2

Memory of 

cycles

Preset value

On power-up

Delay

Seconds

Reset

The ‘UP’ (

5

) key at the front of the instrument gives access to a list of func

-

tions configurable by the operator. See section 

1.17

 for an explanation on how 

to operate the ‘

fast access

’ menu.

The ‘

Key UP (Fast access)

’ (‘

K.uP

’) menu allows to select which functions will 

be accessible through the ‘fast access’ menu. Select ‘

on

’ to activate each func

-

tion.
• the ‘

Setpoint

1

’ (‘

ALr1

’) function allows to visualize and modify the alarm

setpoint through the ‘fast access’ menu.
• the ‘

Setpoint

2

’ (‘

ALr2

’) function allows to visualize and modify the alarm

setpoint through the ‘fast access’ menu.
• the ‘

Memory of maximum

’ (‘

MAX

’)

 

or

 

Memory of minimum

’ (‘

MIn

’) func

-

tions allow to visualize the maximum or minimum reading value stored in 

memory. To reset this value, visualize the memory value at the ‘fast access’ 

menu with key UP (

5

) and when message ‘

rSt

’ is displayed, press (

<

) to re

-

set.

• the ‘

Memory of cycles

’ (‘

cYcL

’)

 

function allow to visualize and reset the 

memory of cycles. To reset this value, visualize the memory value at the ‘fast 

access’ menu with key UP (

5

) and when message ‘

rSt

’ is displayed, press (

<

to reset. The memory of cycles countes ‘+1’ each time a reset alarm occurs 

(‘on_AL’ / ‘to_0’ or ‘to_P’) or a reset by ‘overrange’ / ‘underrange’ occurs.
• the ‘

Preset value

’ (‘

PrSt

’)

 

function allows to visualize and modify the preset 

value configured.

1.19.12 Fast access

If only a single function is selected for the ‘fast access’ menu, press

-

ing the the ‘UP’ (

5

) key will shortly display the function name and 

then automatically jump to the function value.

1.19.13 

Super fast access

The ‘LE’ (

3

) key at the front of the instrument can be configured to 

activate several functions. Only one function can be assigned to the 

‘LE’ (

3

) key

• the ‘

No function

’ (‘

nonE

’)

 

value assigns no function.

• the ‘

Front reset

’ (‘

F.rSt

’) value assigns the reset function.

• the ‘

Alarm unlock

’ (‘

A.Lck

’)

 

value assigns the manual unlock of the 

alarms function, for instruments with the ‘

Locked alarms

’ (‘

A.Lck

’) 

function activated 

(see section 1.19.11)

•  the  ‘

Reset and alarm unlock

’  (‘

Fr.AL

’)  assigns  the  two  previous 

functions to the same button.

1.19.14 

Menu ‘Key LE’

Key LE

Front reset

Alarm unlock

No function

Reset and alarm unlock

Содержание S40-C1

Страница 1: ...with 4 digit display Fast access to alarm setpoints special modes for fast counting and for slow ratemeter applications on power up function configurable reading brightness Universal AC and DC power...

Страница 2: ...15 Direct configuration for most usual sensor at the SnSr Auto menu see section 1 19 10 Function Trigger Sense helps to detect the correct trigger level see section 1 13 Multiple display filters memor...

Страница 3: ...tor 1 to 9999 and configurable divider factor 1 to 9999 For low frequency applications the SLOW mode provides the best response time for each application see section 1 15 Maximum frequency up to 500 K...

Страница 4: ...n sor parameters to the values indicated in the table The table also indicates the typical con nections for each type of sensor Param eters can be manually modified Connections are indicated for a sin...

Страница 5: ...d control options relays analog outputs serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front s...

Страница 6: ...restart power up or configuration change is used for internal initialization and will not be counted as impulse 1 14 Function cycle counter 1 15 SLOW mode The trigger level is automatically configured...

Страница 7: ...ENTER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access me...

Страница 8: ...e Impulses input at channel A Channel B disabled Access the Decimal point dP menu to select the decimal point position Move the decimal point by pressing the LE 3 key Configure the function mode selec...

Страница 9: ...hen channel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 4 Configuration for cnI 3 Configuration menu for mode counter control add substract cn...

Страница 10: ...in formation on the SLoW mode in case of unstable signals activate the average filter AVr func tion It activates a recursive filter on the reading the filter is stronger for higher values from 0 0 to...

Страница 11: ...the SLoW parameter configuring the tIME parameter between 1 and 1000 seconds Configure the nuMb parameter between 1 and 32 impulses See section 1 15 for more in formation on the SLoW mode in case of u...

Страница 12: ...nnel Act r configures the activa tion of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value of the excita tion voltage at 5 Vdc 9 Vdc 15 Vdc an...

Страница 13: ...s at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hysteresis value is passed Value from 0 0 t...

Страница 14: ...tpoint2 ALr2 function allows to visualize and modify the alarm2 setpoint through the fast access menu the Memory of maximum MAX or Memory of minimum MIn func tions allow to visualize the maximum or mi...

Страница 15: ...et FAct menu select yes to load the default factory configuration for the instrument see section 1 21 1 19 20 Factory reset 1 19 21 Firmware version 1 19 16 Menus Overrange underrange The Counter over...

Страница 16: ...unter inhibition Multiplier Divider Preset Preset value 1999 to 9999 Mode Up Down Inhibition Inhibits if chan nel B is high Inhibits if chan nel B is 0 Vdc Multiplier 1 to 9999 Divider 1 to 9999 Confi...

Страница 17: ...3 wire PNP 2 wire PNP 3 wire Push pull TTL CMOS Pick up Inductive Vac 30 V Multiplier 1 to 9999 Divider 1 to 9999 Conf ratemeter Multiplier Divider Time window Seconds SLOW mode Average filter Filter...

Страница 18: ...h To zero To preset Counter underrange Flash To zero To preset 1 20 Full configuration menu cont On alarm Continue To zero To preset Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Alarms Act...

Страница 19: ...ory of cycles 0 Counter overrange flash Counter underrange flash Left zeros off Vexc control off Password off Brightness 3 Alarms 1 and 2 Active off disabled Type maximum Setpoint 1000 Hysteresis 0 co...

Страница 20: ...nt slide out of the housing To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module Place all the set into the housing assuring that the modules...

Страница 21: ...s and regulations 1 25 Warranty This instrument is warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse accident...

Страница 22: ...pt 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per in...

Страница 23: ...yed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more informa...

Страница 24: ...ration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_en pdf Protocol Modbus RTU Functi...

Страница 25: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum an...

Страница 26: ...FEMA ELECTR NICA Series S S40 C1 26 Notes...

Страница 27: ...FEMA ELECTR NICA Series S S40 C1 27 Notes...

Страница 28: ......

Отзывы: