background image

TST

Expanded Startup

WU

FEIG ELECTRONIC GmbH

Page 3 of 18

WU_erweiterte_ Inbetriebnahme4_GB.doc

Contents

1

Other Applicable Documents

3

2

Entering expanded parameterizing mode

3

3

Optimizing door operation

4

3.1

Opening the door .........................................................................................................................4

3.2

Closing the door...........................................................................................................................5

3.3

New request for automatic limit switch calculation .................................................................6

3.4

Correcting the end positions ......................................................................................................6

4

Input parameterizing

6

5

Output parameterizing

6

6

Maintenance counter

7

7

Parameter list

8

Other Applicable Documents

This function description is an addition to the Startup manual.
It describes only additional setting and functions which are not already contained in the Startup manual.

WARNING

The contents of the Startup manual and in particular the safety advisories must be strictly observed.

Entering expanded parameterizing mode

To enter expanded mode a password must be entered.
For this the following parameter must be set:

P.999: 2 = expanded startup mode

Содержание TST WU

Страница 1: ...ANDED STARTUP preliminary public B 2007 05 29 WU_erweiterte_ Inbetriebnahme4_GB doc TST WU Important You must read the Function Description before operating connecting or starting up the door controll...

Страница 2: ...ness and completeness of the information in this document In particular FEIG ELECTRONIC GmbH cannot be held liable for following damages due to faulty or incomplete information Since mistakes can neve...

Страница 3: ...arameterizing 6 5 Output parameterizing 6 6 Maintenance counter 7 7 Parameter list 8 1 Other Applicable Documents This function description is an addition to the Startup manual It describes only addit...

Страница 4: ...by parameter With electronic limit switches is a automatic correction of the limit switch bands possible by activating P 216 2 3 1 Opening the door End switch close End switch open P 230 OPENING Fig 1...

Страница 5: ...door The door movement starts with an close command or after the auto close time has run out so that the CLOSE contactor will be energized The door moves as long as the limit switch or the limit switc...

Страница 6: ...on causes a shift to the bottom 4 Input parameterizing The door controller is able to change the function of the inputs This is done with the help of input profiles The input profiles can be used to a...

Страница 7: ...intenance is due Setting Parameter P 973 to 1 resets the maintenance counter There are various ways for the maintenance notification to be displayed to the user After the maintenance counter has expir...

Страница 8: ...ch 2 limit switch and pre limit switch normally closed 2 Incremental encoder reference switch in lower end position 3 DES 9600 baud 0 210 0 5 Selecting the position calibrated by a deadman move teach...

Страница 9: ...testing in lower end position e g normally closed system i e pneumatic edge 5 Dynamic optical System 1 P Unit Range Inputs Default 501 0000 1402 Function of input 1 see table 1 Input profiles 502 000...

Страница 10: ...22 see table 1 Input profiles A03 0000 1402 Function of input 23 see table 1 Input profiles A04 0000 1402 Function of input 24 see table 1 Input profiles A05 0000 1402 Function of input 25 see table...

Страница 11: ...ithout Without OPEN No 0111 OPEN 1 N C Upper With Without Both Without Without OPEN No 0112 OPEN 1 N O 3 Upper Without With Both Without Without OPEN No 0114 OPEN airlock N O Intermediate stop With Wi...

Страница 12: ...Intermediate stop 2 Upper With With From outside Without Without Pull Swit ext No 0209 Pull switch OPEN STOP CLOSE STOP N O 1 Intermediate stop 2 Upper Without With Both Without Without Pull switch No...

Страница 13: ...Without Without Dead man No 0701 CLOSE N O With Without Without Close No 0801 Locking in lower end position deadman not possible N O Without Without Locked Closed No 0802 Locking in lower end position...

Страница 14: ...ate stop pre limit switch N O Without Without PreLim Interm No 1104 Safety edge pre limit switch N O Without Without PreLimit Edge No 1105 Safety edge pre limit switch N C Without Without PreLimit Edg...

Страница 15: ...sing th input N C As before As before With Both Without Without Photo eye No 1404 Safety input A Stop during opening and closing N C Upper Without With No Without Without Photo eye No 1405 Safety inpu...

Страница 16: ...ed traffic light on inside of Door 1 1221 Flashing red traffic light on inside of Door 1 1222 Red traffic light on inside of Door 2 1223 Flashing red traffic light on inside of Door 2 1224 Red traffic...

Страница 17: ...lue of the absolute encoder 13 V Current reference voltage 14 C Temperature inside the housing in Celsius 15 C Temperature inside the housing in Fahrenheit 16 Reserved 17 Reserved 18 Rotation speed of...

Страница 18: ...bnahme4_GB doc P Unit Range Service Modes Default 973 0 1 Reset service counter Reset 1 Cancel 0 0 980 0 2 Service mode 0 Au Automatic opening and closing self retaining 1 Hc Deadman Close Manual Clos...

Отзывы: