3.3 New request for automatic limit switch calculation
If automatic calculation of the limit switch bands is factory set (P.216 = 2), the door movement is
automatically optimized.
Here the stop position is measured and the optimum limit switch band is set.
If these settings will not fit to the door, you can set them manually as shown in the following.
You can also make a request for a new calculation. To do this, set P.215 to 1 and save it.
3.4 Correcting the end positions
Parameters P.221 and P.231 can be used to shift the end positions.
Changing these parameters in the positive direction causes the end position to be shifted up.
Changing in the negative direction causes a shift to the bottom.
4 Input
parameterizing
The door controller is able to change the function of the inputs.
This is done with the help of input profiles. The input profiles can be used to assign pre-programmable
functions to the inputs.
Settings are possible for inputs 1 to 10 and 21 to 28 (TST RWU only).
P.501 = Input 1
....
P.509 = Input 9
P.50A = Input 10
P.A01 = Input 21
....
P.A08 = Input 28
The possible input functions for inputs can be found in the following table in the parameter list of this
description:
Table 1: Input profiles
5 Output
parameterizing
The door controller is able to change the function of relay outputs.
This is done with the help of output profiles. The output profiles can be used to assign pre-programmable
functions to the outputs.
Output relays K1 and K2 on the TST WU door controller can be set as well as K3 to K6 when used with TST
RWU.
P.701 = Output K1
P.702 = Output K2
P.703 = Output K3
P.704 = Output K4
P.705 = Output K5
P.706 = Output K6