Operating Instructions
VEK CN1-1
10 12/11
FEIG ELECTRONIC GmbH
2.4.2 Counter
Hysteresis
With the counter hysteresis you can set the amount of vehicles that have to leave the facility after the “OPEN
SPACE COUNTING” or the “PASSING VEHICLE COUNTING” have reached the maximum and triggered the
output relay. Factory default is 0.
Display
State Setting
1234
Normal Operation
M long
→
SyS
→
S
oc
M 1 x short
→
HyS
= counter hysteresis
HYS
1234
(alternating)
Display counter
hysteresis
M short
→
continue, next menu item
M long
→
End
= back to normal operation
∧
or
∨
→
change threshold
1234
(one flashing
digit)
Change counter
hysteresis
1...9999
∧
or
∨
→
Digit +/- 1
∧
or
∨
1 sec.
→
fast scroll
∧
or
∨
3 sec.
→
10´s
→
100´s
→
1000´s
M short
→
100´s
→
10´s
→
1´s
→
cancel
M long
→
Skor
= save
2.4.3 Counter
Level
The maximum and minimum range of the total counter can be adjusted using this menu. This enables the counter
to automatically adjust the total in case the maximum or minimum level reached to prevent an incorrect counter to
continue. The default is 9999 for upper and -999 for the lower level.
Display
State Setting
1234
Normal operation
M long
→
SµS
→
S
oc
M 2 x short
→
SkP~
= upper level 0…9999
M short
→
SkP_
= lower level -999…0
SkP~
/
_
1234
(alternating)
Display counter level
M short
→
continue, next menu item
M long
→
End
= back to normal operation
∧
or
∨
→
change counter level
1234
(one flashing
digit)
Change counter level
0...9999
∧
or
∨
→
Digit +/- 1
∧
or
∨
1 sec.
→
fast scroll
∧
or
∨
3 sec.
→
10´s
→
100´s
→
1000´s
M short
→
100´s
→
10´s
→
1´s
→
cancel
M long
→
Stor
= save