CONTROL OPERATION 

 

Electronic Control 

 

This unit is equipped with a CAREL PJEZ temperature control. The control parameters 
are set at the factory and cannot be manually changed in the field. Control parameter 
changes can only be made by downloading a new set of parameters via a program chip 
supplied by Federal Industries.  
 
 

Operation 

The control uses two sensors, one located in the air stream and one located on the 
evaporator coil. The sensor located in the air stream is referred to as the temperature 
control sensor. The sensor located on the evaporator coil is referred to as the coil 
sensor. 
 
The temperature control sensor is located inside the center tower at the top. The sensor 
location is critical for proper operation on the unit. Do not move or relocate this sensor. 
 
The coil sensor is strapped to the evaporator coil. This sensor location is critical for 
proper operation of the unit. Do not move or relocate this sensor. 
 
The temperature control is set to cut in at 39 degrees F. The Temp control cuts out at 
14 degrees F at the coldest setting “9” and 28 degrees F at the warmest setting, ‘1’ on 
the control display. 
 
The temp control turns off the refrigeration system when you “press and hold” the top 
arrow / power button for approx. 3 seconds until “OFF” flashes on display. 
 

Defrost Cycle 

The CAREL control is programmed to initiate defrost via two different methods. There 
are 3 programmed defrost cycles in the case which will initiate a defrost cycle every 8 
hours. The unit does not have a time clock so the defrost cycles cannot be set for any 
specific time of day. 
 
The unit also has an ‘On demand’ defrost feature that will initiate a defrost when the 
temperature differential between the evaporator temperature and the air temperature is 
more than 15 degrees for 5 minutes after 30 minutes into the refrigeration cycle.  
 

 

Maximum Run Timer 

The unit is equipped with a maximum run timer that is preset at the factory for 75 
minutes on. If the temperature control does not reach cut out set point after running for 
one hour, the timer will turn the compressor off for a minimum of 2 minutes.  

 
 
 
 

Содержание ECSS40

Страница 1: ...0 MODELS INSTALLATION OPERATIONS MANUAL KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice FEDERAL INDUSTRIES 215 Federal AVE Belleville WI 53508...

Страница 2: ...0 CONDENSATE EVAPORATOR 11 CONDENSATE PUMP OPTIONAL 11 SHELVES 12 13 OPERATING INSTRUCTIONS 14 USER CONTROLS 14 POWER SWITCH 14 LIGHT SWITCH 14 ELECTRONIC CONTROL 14 16 INITIAL START UP 17 PLACING PRO...

Страница 3: ...s contain technical instructions are intended only for persons qualified to perform electrical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury or...

Страница 4: ...occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE This is impor...

Страница 5: ...umidity locations such as near cases with water misting or fogging devices Failure to locate this case as stated will reduce the performance of your Island display and will affect temperature of inter...

Страница 6: ...rd is properly sized to the amperage requirements of the case See the electrical data plate located on the rear exterior of the case for the proper circuit size for each case The cord is factory insta...

Страница 7: ...this manual Leveling The Case The case must be level for proper drainage of defrost water to the condensate pump Check the level of the case where the display overhangs the base Adjust levelers as ne...

Страница 8: ...SIDE PANEL HOOK 1 4 TURN PANEL RETAINER SCREWS TYPICAL RIGHT SIDE PANEL Typical Panels Removal 1 Loosen the 2 turn retainer screws from top of panel The screws will stay on the panel even after they a...

Страница 9: ...EVAPORATOR OR OPTIONAL CONDENSATE PUMP 7 8 BACK PANEL ELECTRICAL CONNECTION LOCATION FOR OPTIONAL POWER CORD 6 5 7 0 7 6 Base Component Layout ECSS60SC Self Contained 60 41 CONTROL PANEL LOCATION SLID...

Страница 10: ...POWER CORD 2 2 SITE GLASS 5 8 SUCTION LINE 3 8 LIQUID SOLENOID LIGHT POWER SUPPLY 40 91 40 32 4 4 6 5 Base Component Layout ECSS60R Remote CONTROL PANEL LOCATION CONDENSATE PUMP REFRIGERATION FLOOR AC...

Страница 11: ...oduce a large amount of condensate water To ensure that adequate evaporator capacity is available a high wattage heater is used The heater turns off automatically when the water level in the pan drops...

Страница 12: ...red tower slot on one side of the case Place the additional shelf brackets in the same height level on the opposite end of case The short brackets must go on the short end and 2 long brackets must go...

Страница 13: ...the socket is not being used for a shelf light the cap must be plugged into socket to prevent contamination and moisture out of the socket 7 Plug in each shelf light by aligning the male pins on the a...

Страница 14: ...ns on and off the interior lights of unit This switch is located below the lift up panel on the unit base Electronic Control This control is located behind a lift up panel on the unit base Using Elect...

Страница 15: ...n the display will read the relative current case temperature on initial startup this would be room temperature The compressor run indicator will illuminate on the display meaning that the compressor...

Страница 16: ...defrost mode In order to initiate a manual defrost press and hold the button approx 5 seconds The control will read dEF while the button is being held The defrost is initiated when the defrost mode i...

Страница 17: ...shelving area Determine desired shelving location before placing product in case Product must be removed to readjust shelf location Allow a minimum of 2 between top of product and bottom of shelf Do n...

Страница 18: ...nect power to the unit 2 On ECSS40 Remove the nose panel and on ECSS60 remove the side panel on left side of case next to the controls Carefully vacuum the front surface of condenser coil Take care no...

Страница 19: ...t electrical damage to the case NOTICE Shut off lights and power switches and remove all products from case Allow sufficient time for the unit to reach room temperature before proceeding with cleaning...

Страница 20: ...ures to prevent hazing and yellowing of material Note Detergents are not recommended and do not use abrasive cleaners or pads to prevent scratching of surfaces TOWER SIDE PANEL LATCH 4 SHELVES 6 SHELF...

Страница 21: ...soapy water with a damp cloth and allow to dry DO NOT use solvents such as Acetone Benzene Carbon Tetrachloride and Lacquer Thinners 8 IMPORTANT Cleaning the clear acrylic plastic front air deflector...

Страница 22: ...or a blocked evaporator coil Check that paper or foreign materials are not blocking evaporator If the evaporator coil is blocked due to excessive frost put into manual defrost Excessive frost can buil...

Страница 23: ...ase has a receiver tank large enough to hold all the charge you maybe able to pump down the system when service is required If moisture or liquid is observed around or under a Federal Industries case...

Страница 24: ...es case you should evacuate the refrigerant charge before shipment Federal Industries recommends that the charge be evacuated into a recovery system to prevent the possibility of HCFC s from being rel...

Страница 25: ...rature control is set to cut in at 39 degrees F The Temp control cuts out at 14 degrees F at the coldest setting 9 and 28 degrees F at the warmest setting 1 on the control display The temp control tur...

Страница 26: ...200 psi Remote High Press Switch Cut Out 400 psi The remote models are designed to use 448 449A refrigerant and shipped from the factory with the evaporator coil expansion valve sight glass and refri...

Страница 27: ...tion lines 4 Suction line must be insulated the entire length with Armaflex or equivalent Do not run liquid line inside insulation with suction line 5 The remote high low pressure control must be moun...

Страница 28: ...Guard Evaporator Fan 64 18015 64 18015 Electrical Components LED light bar 8 Before 8 1 18 42 19038 42 19038 LED light bar 10 1 Before 8 1 18 42 19038 1 42 19038 Shelf Lamp Cord Before 8 1 18 43 1906...

Страница 29: ...n SA2928 SA2928 Optional Power Cord 43 19090 43 19090 Optional Condensate Pump 47 18980 47 18980 Miscellaneous Components Display Deck Plastic Left Right 15 18857 L 15 18857 R 15 19293 L 15 19293 R Fa...

Страница 30: ...MP SHELF LAMP R BL SHELF LAMP IF OPTIONAL CONDENSATE PUMP OR CONDENSATE PAN ARE NOT USED DISCARD WIRES B 22 R 23 G 24 R 22 P R 23 OPTIONAL CONDENSATE PUMP G 24 R 15 BRW BL B B BL B R 3 2 4 1 MAX RUN T...

Страница 31: ...LAMP R BL SHELF LAMP IF OPTIONAL CONDENSATE PUMP OR CONDENSATE PAN ARE NOT USED DISCARD WIRES B 22 R 23 G 24 R 22 P R 23 OPTIONAL CONDENSATE PUMP G 24 R 15 BRW BL B B BL B R 3 2 4 1 MAX RUN TIMER TUR...

Страница 32: ...G 24 G 25 B 17 B 16 R 15 R 14 Y 10 Y 9 R 2 B 1 R 4 B 3 R 20 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B BL R BL SH...

Страница 33: ...C NO POWER SUPPLY TURN FULL CLOCK WISE MAX RUN TIMER 1 4 2 3 R B B BL B BL BRW R 15 G 24 CONDENSATE PUMP OPTIONAL R 23 P R 22 IF OPTIONAL CONDENSATE PUMP OR CONDENSATE PAN ARE NOT USED DISCARD WIRES B...

Страница 34: ...BL TOP LAMP B B R B BL TOP LAMP B TURN FULL CLOCK WISE 208 240V 60Hz 1PH Y 6 R 15 3 2 4 1 MAX RUN TIMER TURN FULL CLOCK WISE RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 RIB RIB TERM BLOCK TEMP PROBE PB...

Страница 35: ...B BL R BL SHELF LAMP R BL B B BL SHELF LAMP SHELF LAMP R BL SHELF LAMP B 22 P R 23 CONDENSATE PUMP G 24 R 15 BRW BL B B BL B R POWER SUPPLY RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 91 19504 8 26 14...

Страница 36: ...14 Y 10 R 2 B 1 R 4 B 3 L2 L1 N B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHEL...

Страница 37: ...3 4 5 6 7 G 26 RIBBON CABLE POWER SUPPLY R B B BL B BL BRW R 15 SHELF LAMP BL R SHELF LAMP SHELF LAMP B BL B BL R SHELF LAMP BL R B BL B BL B B B BL Y 6 R B B B B B R R R R TOP LAMP TOP LAMP B BL BLK...

Страница 38: ...B B R B R B BL TOP LAMP B B R B BL TOP LAMP B B R B BL TOP LAMP B 208 240V 60Hz 1PH Y 6 R 15 RIBBON CABLE G 26 1 2 3 4 5 6 7 8 9 10 11 RIB RIB TERM BLOCK TEMP PROBE PB1 DEFROST PROBE PB2 POWER SWITCH...

Страница 39: ...B B BL B BL R BL SHELF LAMP R BL B B BL SHELF LAMP SHELF LAMP R BL SHELF LAMP B 22 P R 23 CONDENSATE PUMP G 24 R 15 BRW BL B B BL B R POWER SUPPLY G 26 91 19504 1 5 1 18 ECSS40SC TECHUMSEH RIB RIB TE...

Страница 40: ...SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B B R B BL R BL SHELF LAMP B B BL B POWER SUPPLY IF OPTIONAL CONDO...

Страница 41: ...ER SUPPLY R B B BL B BL BRW R 15 SHELF LAMP BL R SHELF LAMP SHELF LAMP B BL B BL R SHELF LAMP BL R B BL B BL B B B BL Y 6 R B B B B B R R R R TOP LAMP TOP LAMP B BL BLK B B B BL B BL B B R R SHELF LAM...

Страница 42: ...BL B BL B B B R B R B BL TOP LAMP B B R B BL TOP LAMP B B R B BL TOP LAMP B 208 240V 60Hz 1PH Y 6 R 15 G 26 RIB RIB TERM BLOCK TEMP PROBE PB1 DEFROST PROBE PB2 POWER SWITCH TERM BLOCK L1 TERM BLOCK L2...

Страница 43: ...FANS R 11 B 5 B 13 R 12 G 25 B 17 B 16 R 15 R 14 Y 10 Y R 2 B 1 R 4 B 3 L2 L1 N SHELF LIGHT QUANITY MAY VARY ON DIFFERENT MODELS PRESS SWITCH Y B 2 X 4 IF OPTIONAL CONDO PUMP HOSE HEATER IS USED TIE H...

Страница 44: ...B BL SHELF LAMP B BL B BL SHELF LAMP B BL B BL SHELF LAMP B BL IF OPTIONAL CONDO PUMP HOSE HEATER IS USED TIE HEATER WIRES TO B22 R23 B 22 P R 23 CONDENSATE PUMP G 24 B W G GREEN B BLACK R RED W WHIT...

Страница 45: ...SUPPLY 91 19629 2 12 27 18 ECSS40R ITC LED B 16 G GREEN B BLACK R RED W WHITE Y YELLOW BL BLUE COLOR CODE B BL B BL B BL IF OPTIONAL CONDO PUMP HOSE HEATER IS USED TIE HEATER WIRES TO B22 R23 B B RIB...

Страница 46: ...SHELF LAMP B BL IF OPTIONAL CONDO PUMP HOSE HEATER IS USED TIE HEATER WIRES TO B22 R23 B W G GREEN B BLACK R RED W WHITE Y YELLOW BL BLUE COLOR CODE B BL B BL B BL TOP LAMP B BL TOP LAMP B BL TOP LAMP...

Отзывы: