![Federal Signal Corporation Informer100 Speaker Скачать руководство пользователя страница 23](http://html2.mh-extra.com/html/federal-signal-corporation/informer100-speaker/informer100-speaker_description-specifications-and-installation-manual_3837623023.webp)
23
Installation
Description, Specifications, and Installation Manual
Federal Signal
www.fedsig.com
I-IP100AC 120/240 Vac Model
• JP4 is used for relay 1 (pins 1 and 2) and provides an interface for AC powered strobes
using (pins 5 and 6).
• JP6 and JP7 can be used for access to 120 or 240 Vac to power strobes or other
external equipment.
• JP8 is used for incoming AC power. Verify switch on the power supply is set correctly.
• JP9 is prewired to the power supply.
Figure 14 AC Controller Board
LAN Communications
JP3
Inter-board communications
AC
In
JP4
External Inputs
Dry contact closures
See NOTE.
JP7
JP8
JP9
L1/Hot
L1/Hot
JP1
JP2
(Factory wiring)
(Factory wiring)
JP6
L1/Hot
L1/Hot
Serial Port
4
JP5
3
2
1
Visual
L2/NUE
GND
L2/NUE
GND
L2/NUE
GND
L2/NUE
GND
DC PWR+
External
Device
120/240 VAC
to 24 VDC
Power Supply
120
To Driver
To Temperature
Sense
100 W Amp
240
Fuse
(Factory wiring)
Fuse
Fuse
AC LOAD RLY 2
AC POWER
264V 1A Max
DC LOAD+ RLY 2
30V 5A Max
N.O.
250V 2A Max
RLY 1
COM