FEC Remote Lighting Controller V4 HP0832
User Installation and Operation Manual
© Interleader Ltd 2020
22 of 64
26/08/2020
6.4 Setup Systems
6.4.1 Set Channel Timeouts
The time-out period for each
channel
to be set in the range (default 15 minutes):
a) 10 seconds to 1 minute (in 10 second intervals), and
b) 1 to 60 minutes (in 1 minute intervals)
Changes are made simply using the F1 & F2 keys and then either quitting or saving when happy
with the new value.
NB: The provision of very short time-out periods is to allow the driving of latching infrastructure
(either direct contactor switching or a BMS, for example). Such short periods would not normally
be used to drive lighting circuits directly.
When using Windsock alert (as required in certain territories) ensure that the channel timeout
chosen is longer than the windsock alert period (default 10 minutes).
Содержание HP0832
Страница 64: ...End of Document...