3

Vandalism

If the unit is installed where vandalism may be a problem, the assembly 

should be protected and secured . On 

1

2

" through 2" (15-20mm) units, the 

handles of shutoff valves can be removed to discourage tampering . On 

2

1

2

" through 10" (65-250mm) units, a chain can be looped through both 

shutoff valve handwheels and locked in position to prevent tampering . 

Testcock handles can also be removed . On backflow prevention assem-

blies installed in conjunction with fire sprinkler systems, a tamper switch 

can be placed on the OS&Y shutoff valves that will trigger an alarm if an 

unauthorized closure should occur .
A protective enclosure can be installed over the unit to discourage van-

dals . If an enclosure is used, it should be installed so that adequate clear-

ance is available for maintenance and testing . Consult local codes before 

installing any type of protective enclosure .

Testing

All mechanical devices should be inspected on a regular basis to ensure 

they are working correctly . The assembly should be tested at time of ini-

tial installation, after servicing or maintenance, and at least annually there-

after . Acceptable test procedures are published by Foundation for Cross-

Connection Control and Hydraulic Research at the University of Southern 

California (USC), The American Water Works Association (AWWA), The 

American Society of Sanitary Engineering (ASSE Series 5000) and the 

Canadian Standards Association (CAN/CSA B64 .10) . Please consult the 

regulatory authority in your area for more specific information . 

MAINTENANCE MANUAL SERIES 850, 856, 870V & 876V 2

1

2

"- 10" (65 – 250mm)

Troubleshooting

  Symptom #1  

CauSe: 

Solution:

  Check fails to hold 1.0 psid minimum 

A. Debris on sealing surfaces 

Inspect and clean

   

B. Leaking shutoff valve 

Inspect and clean, or repair

   

C. Damaged seat or seat disc 

Disassemble and replace

   

D. Spring stem not moving freely 

Inspect for debris or damage

  Symptom #3 (DCDa only) 

CauSe: 

Solution:

  Low flow passing through the 

A. Mainline check fouled 

Inspect and clean, or repair

  mainline valve (DCDA only) 

B. Bypass plugged (DCDA only) 

Inspect and clean

  Symptom #2 

CauSe: 

Solution:

  Chatter during flow conditions  

A. Worn or damaged parts 

Inspect and replace

Содержание 856

Страница 1: ...ing this equipment Table of Contents Features and Operating Procedures 2 How to Order Parts 2 Trouble Shooting Guide 3 Vandalism 3 Testing 3 Freeze Protection Procedures 4 General Service Procedures 4...

Страница 2: ...led in the vertical orientation must include vertical support under the second check body section Double Check Detector Assemblies Bypass Operation All low flow demands up to a minimum of three GPM ar...

Страница 3: ...rrectly The assembly should be tested at time of ini tial installation after servicing or maintenance and at least annually there after Acceptable test procedures are published by Foundation for Cross...

Страница 4: ...check module until all water inside valve drains back out through inlet drain 7 If you blowout the piping downstream of the backflow assembly using compressed air Connect the air supply to the outlet...

Страница 5: ...g to help hold O ring in place during reassembly Series 870V and 876V Apply a thin coating of the lubricant supplied in the repair kit to the O ring groove in the 2 check body and position the O ring...

Страница 6: ...eck disc stem threads Lift the arm and remove the check disc Item 6 Inspect sealing surface for debris or damage Replace check disc if necessary NOTE When jam nut Item 16 is tight check disc is design...

Страница 7: ...7 905158 905159 905160 Items 3 3 1 3 2 3 4 4 4 1 4 2 5 RUBBER PARTS KIT ALL Part 905249 905163 905164 905165 Items 2 1 3 1 6 15 26 35 35 1 45 45 1 COVER ASSEMBLY With Bulkhead Part 905167 905168 90516...

Страница 8: ...26 35 35 1 45 45 1 COVER ASSEMBLY Inlet Check ALL Part 905167 905168 905169 905170 905171 Items 2 2 1 15 COVER ASSEMBLY Outlet Check ALL Part 905244 905245 905246 905247 905248 Items 2 2 1 15 BULKHEA...

Страница 9: ...ammer or other causes of excessive water pressure Seat discs damaged in such a manner should be replaced and not turned over to be reused 3 Check Seat Ring Replacement a The seat rings are threaded in...

Страница 10: ...Nitrile 11 Washer Stainless Steel 12 Screw Stainless Steel 13 Spring Stainless Steel 30 Test Cock Bronze 35 Seat Ring Bronze 36 O ring Buna N 40 Ball Valve Bronze 40 1 Ball Valve Bronze 40 2 Ball Val...

Страница 11: ...ead loss Cast ductile iron bodies for lighter weight Lowest installed cost Saves on labor and material Choice of cost saving N Shape designs revolutionary vertical designs or conventional in line desi...

Страница 12: ...e sole and exclusive remedy for breach of warranty and the Company shall not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of...

Отзывы: