3 Installation
- 14 -
Remarks If the input voltage and the frequency are out of this range, the UPS will
become the following state or be damaged.
When the UPS is turned on:
The UPS will become the "input error at startup". In this case, the UPS
cannot be started up.
While the UPS is operating:
"Abnormalities of input voltage" is detected and the battery operation is
performed. If the UPS is connected to an input power supply which gets
out of this range frequently, by repeating the charge and discharge of
the battery, the battery will be in an empty state or will become the
cause of deterioration.
Note) The input frequency of the using area is chosen automatically.
2.
The specification of the terminal block is as follows. Select the crimp contact which
is suitable for specification.
〈
M-UPS050AD2B
〉
〈
M-UPS075AD2B, M-UPS100AD2B
〉
UPS side
Specification
Connect with
Terminal
marking
Connection
Figuration
L1/R
AC input
(un-grounding side)
L2/S
AC input
(un-grounding side)
PE(G)
Ground
(protective
grounding)
l1/U
AC output
(un-grounding side)
Input and
output
terminal block
l2/V
AC output
(un-grounding side)
5 pole
screw
terminal
(M5)
Input power supply
and output system
UPS side
Specification
Connect with
Terminal
marking
Connection
Figuration
L1/R
AC input
(un-grounding side)
L2/S
AC input
(un-grounding side)
PE(G)
Ground
(protective
grounding)
PE(G)
Ground
(protective
grounding)
l1/U
AC output
(un-grounding side)
Input and
output
terminal block
l2/V
AC output
(un-grounding side)
6 pole
screw
terminal
(M8)
Input power supply
and output system