2 Outline
- 6 -
At the automatic bypass operation
When the abnormalities occurred in the UPS during the normal operation, the UPS
switches to the bypass operation automatically. During the bypass operation, the UPS
sends the input voltage to the output directly and supplies the electric power to the
connection device. In this operation state, even if the power failure occurs, the UPS
becomes the power failure state without switching to the battery operation.
+
Bypass
AC/AC converter
Boost chopper
Battery
Charger
[ UPS ]
To connection device
:Power is fed
An error
occurs inside
the UPS
- The abnormalities inside the UPS
:Power is not fed
Output
Input power supply
Electricity flow during automatic bypass operation
At the manual bypass operation
It is possible to switch to the bypass operation manually during the normal operation.
Press the RESET switch and the BYPASS switch for approximately 3 seconds
simultaneously to switch to the bypass operation.
When the switches are pressed for approximately 3 seconds simultaneously again, the
UPS returns to the normal operation. In this operation state, even if the power failure
occurs, the UPS becomes the power failure state without switching to the battery
operation.
+
Bypass
AC/AC converter
Boost chopper
Battery
Charger
[ UPS ]
To connection device
:Power is fed
:Power is not fed
Output
Input power supply
Switching to the bypass
operation manually
Electricity flow during manual bypass operation