3.1 Installing the UPS
- 9 -
The following space is required for installation
•
The UPS draws air in through the vents on the front of the UPS and
exhausts it through the cooling fan on the back of the UPS. A minimum
of 10 cm of space is required on the front and back of the UPS.
When performing maintenance on the UPS, a space of approximately 1 m
is required in front of and behind the UPS.
The recommended environment is as follows.
Item
Recommended environment
Temperature
15 to 25 C
Humidity
30 to 70% (no condensation)
Front
Rear
UPS
10 cm
or more
10 cm
or more
Intake air
Exhaust
Front
UPS
Rear
Space for
maintenance of
cooling fan
Space for
maintenance of
cooling fan/batteries